1
1-392
Before Installing the Ceiling Panel
(1) Remove the air-intake grille and air filter from the ceiling
panel.
a) Remove the 2 screws on the latch of the air-intake
grille. (Fig. 2-14) (Reattach the air-intake grille after
installation of the ceiling panel.)
Fig. 2-14
b) Slide the air-intake grille catches in the direction shown
by the arrows
to open the grille. (Fig. 2-15)
1
1
Fig. 2-15
c) With the air-intake grille opened, remove the grille
hinge from the ceiling panel by sliding it in the direction
shown by the arrow
. (Fig. 2-16)
2
Fig. 2-16
(2) Removing the corner cover.
a) Slide the latches in the direction of the arrow
to
disconnect the hinges (3 locations). Then, remove
the air-intake grille in the direction of the arrow
.
(Fig. 2-17)
1
2
1
1
2
2
1
Fig. 2-17
Installing the Ceiling Panel
The power must be turned ON in order to change the flap
angle. (Do not attempt to move the flap by hand. Doing so may
damage the flap.)
(1) Hang the temporary latches on the inside of the ceiling
panel to the receptacle on the unit to temporarily attach
the ceiling panel in place. (Fig. 2-18)
HOW TO INSTALL THE CEILING PANEL
4-Way Cassette 60 × 60 Type (Y1 Type)
Checking the unit position
(1) Check that the ceiling hole is within this range:
600 × 600 mm
(2) Confirm that the positions of the indoor unit and the ceiling
are as shown in the diagram. If the positions of the ceiling
surface and unit do not match, air leakage, water leakage,
flap operation failure, or other problems may occur.
CAUTION
Never place the panel face-down. Either hang it
vertically or place it on top of a projecting object.
Placing it face-down will damage the surface. (Fig. 2-12)
A
must be within the range of 13 – 18 mm. (Fig. 2-12)
If not within this range, malfunction or other trouble may
occur.
A
Main unit
Ceiling side
Ceiling opening
dimension
Fig. 2-12
Do not touch the flap or apply force to it. (Fig. 2-13)
(This may cause flap malfunction.)
Flap
Fig. 2-13
Air-intake grille
Air-intake grille hinge
Ceiling panel
Corner cover
Ceiling panel
Corner cover
Push
Screw
Latch
SM830211-07̲PAC-i.indb 392
SM830211-07̲PAC-i.indb 392
2013/09/17 22:48:25
2013/09/17 22:48:25
Summary of Contents for U-100PEY1E5
Page 536: ... MEMO 1 526 ...
Page 540: ... MEMO 2 4 ...
Page 549: ...3 9 3 3 1 Indoor Units Ducted Type S 36PN1E5 S 45PN1E5 S 50PN1E5 Electric Wiring Diagram ...
Page 551: ...3 11 3 3 2 Outdoor Units Single phase U 50PE1E5 ...
Page 552: ...3 12 3 3 2 Outdoor Units Single phase U 50PE1E5 ...
Page 553: ...3 13 3 3 2 Outdoor Units Single phase U 60PE1E5 U 71PE1E5 䡵 ...
Page 554: ...3 14 3 3 2 Outdoor Units Single phase U 100PE1E5 U 125PE1E5 U 140PE1E5 䡵 ...
Page 555: ...3 15 3 3 2 Outdoor Units Single phase U 60PEY1E5 U 71PEY1E5 ...
Page 556: ...3 16 3 3 2 Outdoor Units Single phase U 60PEY1E5 U 71PEY1E5 ...
Page 558: ...3 18 3 3 2 Outdoor Units 3 phase U 71PE1E8 ...
Page 559: ...3 19 3 3 2 Outdoor Units 3 phase U 100PEY1E8 U 125PEY1E8 ...
Page 560: ...3 20 3 3 2 Outdoor Units 3 phase U 100PE1E8 U 125PE1E8 U 140PE1E8 U 140PEY1E8 ...
Page 594: ...4 34 4 HIC PCB A746895 U 60PE1E5 U 71PE1E5 CN VDC U P V W N CN VDC 4WAY Valve CN 20S ...
Page 595: ...4 35 4 HIC PCB continued A746846 U 100PE1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 597: ...4 37 4 HIC PCB A746846 U 100PEY1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 598: ...4 38 4 HIC PCB continued A746847 U 125PEY1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 602: ...4 42 4 HIC PCB A747248 U 100PEY1E8 U 125PEY1E8 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 738: ... MEMO 8 34 ...
Page 739: ...201309 ...