1
1-340
Case 4
Setting outdoor unit system addresses
(1)
For the basic wiring diagram (Set the system addresses: 1, 2, 3...)
Next press the
<Approximately 15 minutes is required for each system.>
(Automatic address setting is performed in sequence for
all outdoor units from No. 1 to No. 30.
When automatic address setting is completed, the units
return to normal stopped status.)
button.
Press the remote controller timer time
button and
button simultaneously. (Hold for 4 seconds or longer.)
(2)
During automatic address setting, “SETTING” blinks on the
remote controller display.
This display disappears when address setting is completed.
If the power cannot be turned ON separately for the indoor and outdoor units in each system:
(The compressors must be run in order to automatically set the indoor unit addresses.
Therefore perform this step after completing the refrigerant tubing work.)
↓
↓
All-systems automatic address setting: Display item code “AA”.
System address
ON
1
2
Outdoor unit control PCB
DIP switch
System address
rotary switch
System address rotary switch (Set to “0” at time of shipment)
10s 20s
ON
OFF
LED1
LED2
PUMP DOWN(CN042)
EEPROM(IC006)
AUTO ADD(CN041)
System address
Rotary switch(S002)
TERMINAL (CN003)
JP007
System address
DIP switch (S003)
Bottom
side
Up side
HIC
Temperature
sensor
SILENT MODE
(CN028,WHT)
RC-P(CN034,RED)
FAN(CN030,WHT)
ROM(CN012,WHT)
OC(CN013,BLU)
EMG(CN014,BRN)
20S(CN09,WHT)
FUSE(30A,F003)
C1(CN021,BLK)
TO(CN022,WHT)
TD,TS(CN023,WHT)
C2(CN020,WHT)
MOV(CN025,WHT)
63PH(CN004,RED)
RC-P(CN032,RED)
System address
No.
System address
10s digit
(2P DIP switch)
System address
1s place
(Rotary switch)
0 Automatic address
(Setting at shipment = “0”)
Both OFF
ON
1
2
ON
OFF
1 (If outdoor unit is No. 1)
Both OFF
ON
1
2
ON
OFF
2 (If outdoor unit is No. 2)
Both OFF
ON
1
2
ON
OFF
11 (If outdoor unit is No. 11)
10s digit ON
ON
1
2
ON
OFF
21 (If outdoor unit is No. 21)
20s digit ON
ON
1
2
ON
OFF
30 (If outdoor unit is No. 30)
10s digit and 20s
digit ON
ON
OFF
ON
1
2
“0” setting
“1” setting
“2” setting
“1” setting
“1” setting
“0” setting
SM830211-07̲PAC-i.indb 340
SM830211-07̲PAC-i.indb 340
2013/09/17 22:48:08
2013/09/17 22:48:08
Summary of Contents for U-100PEY1E5
Page 536: ... MEMO 1 526 ...
Page 540: ... MEMO 2 4 ...
Page 549: ...3 9 3 3 1 Indoor Units Ducted Type S 36PN1E5 S 45PN1E5 S 50PN1E5 Electric Wiring Diagram ...
Page 551: ...3 11 3 3 2 Outdoor Units Single phase U 50PE1E5 ...
Page 552: ...3 12 3 3 2 Outdoor Units Single phase U 50PE1E5 ...
Page 553: ...3 13 3 3 2 Outdoor Units Single phase U 60PE1E5 U 71PE1E5 䡵 ...
Page 554: ...3 14 3 3 2 Outdoor Units Single phase U 100PE1E5 U 125PE1E5 U 140PE1E5 䡵 ...
Page 555: ...3 15 3 3 2 Outdoor Units Single phase U 60PEY1E5 U 71PEY1E5 ...
Page 556: ...3 16 3 3 2 Outdoor Units Single phase U 60PEY1E5 U 71PEY1E5 ...
Page 558: ...3 18 3 3 2 Outdoor Units 3 phase U 71PE1E8 ...
Page 559: ...3 19 3 3 2 Outdoor Units 3 phase U 100PEY1E8 U 125PEY1E8 ...
Page 560: ...3 20 3 3 2 Outdoor Units 3 phase U 100PE1E8 U 125PE1E8 U 140PE1E8 U 140PEY1E8 ...
Page 594: ...4 34 4 HIC PCB A746895 U 60PE1E5 U 71PE1E5 CN VDC U P V W N CN VDC 4WAY Valve CN 20S ...
Page 595: ...4 35 4 HIC PCB continued A746846 U 100PE1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 597: ...4 37 4 HIC PCB A746846 U 100PEY1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 598: ...4 38 4 HIC PCB continued A746847 U 125PEY1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 602: ...4 42 4 HIC PCB A747248 U 100PEY1E8 U 125PEY1E8 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 738: ... MEMO 8 34 ...
Page 739: ...201309 ...