Table of Self-Diagnostic Functions and Corrections (K1 Type)
Wired
remote
controller
display
(Field
supply)
Indoor unit
receiver lamp
Cause
Correction
Nothing is
displayed
Nothing is
displayed
Set the indoor operation switch ON.
E01
displayed
Operating lamp
is blinking.
E14
displayed
Connect the wiring correctly.
E06
displayed
E04
displayed
Standby lamp
is blinking.
1:1 connection (Single type)
Indoor operation switch is OFF.
Indoor unit power is not ON.
Automatic address setting has not been
completed.
Inter-unit control wiring is cut or is not
connected correctly.
Indoor-outdoor inter-unit wiring is not
connected correctly.
——————
——————
Group connection
(Simultaneous multi system)
Same at left
Same at left
Remote control
communication wiring is cut
or is not connected correctly.
Same at left
Inter-unit control wiring is
cut or is not connected
correctly.
Turn ON the indoor unit power.
Check the inter-unit control wiring.
Perform automatic address setting
(See section “System Control” for K1 type.)
Refer to “System Control” for K1 type,
and make the correct settings.
Check the remote control communication
wiring.
Perform automatic address setting again.
E15
displayed
E16
displayed
L02
displayed
Both the
Operation lamp
and Standby
lamp are blinking
together.
——————
Indoor unit capacity is too low.
Indoor unit capacity is too high.
Indoor-outdoor unit type mismatch.
Same at left
Same at left
Check that the total capacities of the indoor
and outdoor units are appropriate.
Reverse 2 phases of the outdoor unit
3-phase power and connect them correctly.
P05
displayed
Operation lamp
and Standby
lamp are blinking
alternately.
Reversed phase in the outdoor unit
single-phase or open phase in the
outdoor unit 3-phase power.
Same at left
Connect the units correctly.
Connect the units correctly.
Connect the units correctly
L13
displayed
L04
displayed
Indoor-outdoor units are not setting
correctly.
Connect the units correctly
Same at left
Same at left
Outdoor unit address is
duplicated.
displayed
L07
——————
Perform automatic address setting
(See section “System Control” for K1 type).
P15
displayed
Operation lamp
and Standby
lamp are blinking
alternately.
No gas
Same at left
Check the refrigerant cycle (for gas leaks).
Remote control
communication wiring is
connected to the indoor unit,
however, it is set for
individual operation.
SM830211-07̲PAC-i.indb 330
SM830211-07̲PAC-i.indb 330
2013/09/17 22:48:06
2013/09/17 22:48:06
Summary of Contents for U-100PEY1E5
Page 536: ... MEMO 1 526 ...
Page 540: ... MEMO 2 4 ...
Page 549: ...3 9 3 3 1 Indoor Units Ducted Type S 36PN1E5 S 45PN1E5 S 50PN1E5 Electric Wiring Diagram ...
Page 551: ...3 11 3 3 2 Outdoor Units Single phase U 50PE1E5 ...
Page 552: ...3 12 3 3 2 Outdoor Units Single phase U 50PE1E5 ...
Page 553: ...3 13 3 3 2 Outdoor Units Single phase U 60PE1E5 U 71PE1E5 䡵 ...
Page 554: ...3 14 3 3 2 Outdoor Units Single phase U 100PE1E5 U 125PE1E5 U 140PE1E5 䡵 ...
Page 555: ...3 15 3 3 2 Outdoor Units Single phase U 60PEY1E5 U 71PEY1E5 ...
Page 556: ...3 16 3 3 2 Outdoor Units Single phase U 60PEY1E5 U 71PEY1E5 ...
Page 558: ...3 18 3 3 2 Outdoor Units 3 phase U 71PE1E8 ...
Page 559: ...3 19 3 3 2 Outdoor Units 3 phase U 100PEY1E8 U 125PEY1E8 ...
Page 560: ...3 20 3 3 2 Outdoor Units 3 phase U 100PE1E8 U 125PE1E8 U 140PE1E8 U 140PEY1E8 ...
Page 594: ...4 34 4 HIC PCB A746895 U 60PE1E5 U 71PE1E5 CN VDC U P V W N CN VDC 4WAY Valve CN 20S ...
Page 595: ...4 35 4 HIC PCB continued A746846 U 100PE1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 597: ...4 37 4 HIC PCB A746846 U 100PEY1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 598: ...4 38 4 HIC PCB continued A746847 U 125PEY1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 602: ...4 42 4 HIC PCB A747248 U 100PEY1E8 U 125PEY1E8 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 738: ... MEMO 8 34 ...
Page 739: ...201309 ...