1
1-306
HOW TO INSTALL THE OUTDOOR UNIT
Use concrete or a similar material to make the base, and ensure good drainage.
Ordinarily, ensure a base height of 5 cm or more.
If a drain pipe is used, or for use in cold-weather regions, ensure a height of 15 cm or more at the feet on
both sides of the unit.
(In this case, leave clearance below the unit for the drain pipe, and to prevent freezing of drainage water in cold-
weather regions.)
See the figure shown below for the anchor bolt dimensions.
Be sure to anchor the feet with anchor bolts (M8). In addition, use anchoring washers on the top side.
(Use large square 32 × 32 SUS washers with JIS nominal diameter of 8.) (Field supply)
2- ø12 Anchor bolt hole
(Anchor bolt M8)
Piping direction
Air
Discharge
Air
Intake
Air Intake
ø18 Drain port
2- ø19
Drain port
Drainage Work
Follow the procedure below to ensure adequate draining for the outdoor unit.
For the drain port dimensions
Ensure a base height of 15 cm or more at the feet on both sides of the unit.
When using a drain pipe, install the drain socket (optional part STK-DS13U) onto the drain port.
Seal the other drain port with the rubber cap supplied with the drain socket.
Route the tubing so that it does not contact the compressor, panel, or other parts inside the unit.
Increased noise will result if the tubing contacts these parts.
When routing the tubing, use a tube bender to bend the tubes.
In cold-weather regions, in order to prevent drainage water from freezing, do not install the drain socket
cap. Also take steps to prevent water from accumulating around the unit.
Installing the Outdoor Unit
Routing the Tubing and Wiring
CAUTION
SM830211-07̲PAC-i.indb 306
SM830211-07̲PAC-i.indb 306
2013/09/17 22:48:02
2013/09/17 22:48:02
Summary of Contents for U-100PEY1E5
Page 536: ... MEMO 1 526 ...
Page 540: ... MEMO 2 4 ...
Page 549: ...3 9 3 3 1 Indoor Units Ducted Type S 36PN1E5 S 45PN1E5 S 50PN1E5 Electric Wiring Diagram ...
Page 551: ...3 11 3 3 2 Outdoor Units Single phase U 50PE1E5 ...
Page 552: ...3 12 3 3 2 Outdoor Units Single phase U 50PE1E5 ...
Page 553: ...3 13 3 3 2 Outdoor Units Single phase U 60PE1E5 U 71PE1E5 䡵 ...
Page 554: ...3 14 3 3 2 Outdoor Units Single phase U 100PE1E5 U 125PE1E5 U 140PE1E5 䡵 ...
Page 555: ...3 15 3 3 2 Outdoor Units Single phase U 60PEY1E5 U 71PEY1E5 ...
Page 556: ...3 16 3 3 2 Outdoor Units Single phase U 60PEY1E5 U 71PEY1E5 ...
Page 558: ...3 18 3 3 2 Outdoor Units 3 phase U 71PE1E8 ...
Page 559: ...3 19 3 3 2 Outdoor Units 3 phase U 100PEY1E8 U 125PEY1E8 ...
Page 560: ...3 20 3 3 2 Outdoor Units 3 phase U 100PE1E8 U 125PE1E8 U 140PE1E8 U 140PEY1E8 ...
Page 594: ...4 34 4 HIC PCB A746895 U 60PE1E5 U 71PE1E5 CN VDC U P V W N CN VDC 4WAY Valve CN 20S ...
Page 595: ...4 35 4 HIC PCB continued A746846 U 100PE1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 597: ...4 37 4 HIC PCB A746846 U 100PEY1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 598: ...4 38 4 HIC PCB continued A746847 U 125PEY1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 602: ...4 42 4 HIC PCB A747248 U 100PEY1E8 U 125PEY1E8 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 738: ... MEMO 8 34 ...
Page 739: ...201309 ...