4-48
Note
Related page
• A parameter is designated as follows:
Pr0.00 Parameter No.
Class
• For parameters which No. have a suffix of “
*
”
, changed contents will be validated when
you turn on the control power.
• P.3-32... “Inputs and outputs on connector X4”
Default: [ ]
Pr4.39
Brake release speed setup
Range
Unit
Default
Related
control mode
30 to 3000
r/min
30
P S T F
Set up the speed timing of brake output checking during operation.
Pr4.40
Selection of alarm output 1
Range
Unit
Default
Related
control mode
0 to 40
—
0
P S T F
Pr4.41
Selection of alarm output 2
Range
Unit
Default
Related
control mode
0 to 40
—
0
P S T F
Select the type of alarm issued as the alarm output 1 or 2.
Setup
value
Alarm
Content
[0]
—
ORed output of all alarms.
1
Overload protection
Load factor is 85 % or more the protection level.
2
Over-regeneration alarm
Regenerative load factor is 85 % or more the protection level.
3
Battery alarm
Battery voltage is 3.2 V or lower.
4
Fan alarm
Fan has stopped for 1 sec.
5
Encoder communication
alarm
The number of successive encoder communication errors
exceeds the specified value.
6
Encoder overheat alarm
The encoder detects overheat alarm.
7
Oscillation detection alarm
Oscillation or vibration is detected.
8
Lifetime detection alarm
Life expectancy of capacitor or fan becomes short.
9
External scale error alarm
The external scale detects the alarm.
10
External scale
communication alarm
The number of successive external scale communication
errors exceeds the specified value.
11
Velocity command ON/
OFF output
When Pr7.14(main power off alert detection time) is 10 to
1999, L1-L3 Instant stop for the time set at Pr7.14 above.
For detailed description of alarm types, refer to P.3-49.
Pr4.42
2nd Positioning complete (In-position)
range
Range
Unit
Default
Related
control mode
0 to 2097152
Command
unit
10
P
F
Caution
Note
The INP2 turns ON whenever the positional deviation is lower than the value set up in this
parameter, without being affected by Pr4.32 Positioning complete output setup. (Presence/
absence of positional command is not related to this judgment.)
The command unit is used as the default unit but can be replaced by the encoder unit by
using Pr5.20. Positioning unit selection. Note that when the encoder unit is used, unit of
Pr0.14 Positional deviation excess setup is also changed.
For description of “command unit” and “encoder unit”, refer to P.4-52 “Pr5.20”.
1. Details of parameter
[Class 4] I/F monitor setting
Related page