4-26
Note
Related page
• A parameter is designated as follows:
Pr0.00 Parameter No.
Class
• For parameters which No. have a suffix of “
*
”
, changed contents will be validated when
you turn on the control power.
• P.3-32... “Inputs and outputs on connector X4”
Default: [ ]
Pr2.14
1st damping frequency
Range
Unit
Default
Related
control mode
0 to 3000
0.1 Hz
0
P
F
Pr2.16
2nd damping frequency
Range
Unit
Default
Related
control mode
0 to 3000
0.1 Hz
0
P
F
Pr2.18
3rd damping frequency
Range
Unit
Default
Related
control mode
0 to 3000
0.1 Hz
0
P
F
Pr2.20
4th damping frequency
Range
Unit
Default
Related
control mode
0 to 3000
0.1 Hz
0
P
F
You can set up the 1st to 4th damping frequency of the damping control which suppress
vibration at the load edge.
The driver measures vibration at load edge. Setup unit is 0.1[Hz].
The setup frequency is 1.0 to 300.0[Hz]. Setup of 0 to 9 becomes invalid.
Refer to P.5-37, "Suppression of Machine Resonance" as well before using this parameter.
Pr2.15
1st damping filter setup
Range
Unit
Default
Related
control mode
0 to 1500
0.1 Hz
0
P
F
Pr2.17
2nd damping filter setup
Range
Unit
Default
Related
control mode
0 to 1500
0.1 Hz
0
P
F
Pr2.19
3rd damping filter setup
Range
Unit
Default
Related
control mode
0 to 1500
0.1 Hz
0
P
F
Pr2.21
4th damping filter setup
Range
Unit
Default
Related
control mode
0 to 1500
0.1 Hz
0
P
F
If torque saturation occurs with damping frequency (1st- 4th) enabled, decrease the setup
value, or if the operation is slow, increase it. Usually set it to 0.
The maximum setup value is internally limited to the corresponding damping frequency or
3000 - damping frequency, whichever is smaller.
Refer to P.5-41, "Damping control" as well before using this parameter.
1. Details of parameter
[Class 2] Damping control
Related page
Related page
Caution