Error Messages
270
ZW User's Manual
8-1 Error Messages
Errors for EtherCAT Connection (Sysmac Error Status)
The Sysmac Studio Standard Version displays errors that occur in the EtherCAT system (including Sensor
errors) as Sysmac error status.
Sysmac Error Status Table
This section provides a table of Sysmac error status that is related to the Sensor and describes the event
codes.
Event levels are given as following in the tables.
A version in parentheses in the Event code column is the unit version of the CPU Unit when the event was
added.
Refer to the
NJ-series Troubleshooting Manual
(Cat. No. W503) for all NJ-series event codes.
Abbreviation
Name
Maj
Major fault level
Prt
Partial fault level
Min
Minor fault level
Obs
Observation
Info
Information
Event Code
Event name
Meaning
Assumed cause
Level (*1)
Reference
(Pages)
Maj
Prt
Min
Obs
Info
04D0 0000 Hex
Hardware error Some abnormality
occurred on the
displacement sensor
hardware.
• Hardware damage
14B0 0000 Hex Linearity
correction data
error
The linearity
correction data of the
displacement sensor
is damaged.
• Calibration ROM damage
14B1 0000 Hex Linearity
correction data
read error
Reading of the
displacement sensor
linearity correction
data was not executed
correctly.
• Calibration ROM not inserted
• Calibration ROM damage
14B2 0000 Hex System
setting
error
The system settings
saved to the
displacement sensor
are corrupt.
• The displacement sensor
power was turned OFF dur-
ing saving/loading of system
settings.
14B3 0000 Hex
Bank data error The bank data saved
to the displacement
sensor is corrupt.
• The displacement sensor
power was turned OFF dur-
ing saving/loading of bank
data.
2481 0000 Hex Ethernet
communication
parameter
error
An invalid IP address
is set for the
displacement sensor.
• Invalid IP address setting
7490 0000 Hex
Multiple control
signal input
error
Multiple control
signals turned ON in
the same cycle.
Multiple control signals turned
ON in the same cycle.
ALARM
ALARM
ALARM
ALARM
ALARM
ALARM
Summary of Contents for ZW-C1*AT
Page 17: ...ZW User s Manual 1 15 ...
Page 54: ...Installing the Sysmac Studio 52 ZW User s Manual MEMO ...
Page 74: ...Operating with Sensor Controller 72 ZW User s Manual MEMO ...
Page 120: ...Setting the System 118 ZW User s Manual MEMO ...
Page 138: ...Controll input signal with PC tool 136 ZW User s Manual MEMO ...
Page 262: ...No protocol Connection 260 ZW User s Manual MEMO ...
Page 271: ...8 Troubleshooting Troubleshooting 8 1 Error Messages 270 8 2 Troubleshooting 284 ...
Page 358: ...Connecting by No protocol Communications 356 ZW User s Manual MEMO ...
Page 449: ......