Parallel I/O connection
142
ZW User's Manual
Setting Monitor Focus
With analog output, the relationship between the output value and measured value to be displayed can be set
as desired to convert the measurement result to 4 to 20 mA current or -10 to +10 V voltage before output.
Set the focus to match the connected external device.
The output range can be set by entering the output value for the current or voltage values for any two points.
Example: When setting 4 mA output (1st point) for measured value of 0 mm and 20 mA output for measured
value of 6 mm (2nd point) (current output)
Separate the two specified points by at least 1% of the rated measuring range of the connected Sensor Head or 40
m.
For example, for the ZW-S40, the two measured points must be separated by at least 12 mm × 0.01 = 0.12 mm as the
measuring range is 12 mm (
6 mm).
Item
Setting item
Setting value
Description
Monitor
focus
Monitor focus
ON/OFF (default value)
Sets monitor focus ON/OFF.
Point1
Distance
value
-999.999999 to
-3.000000 (default value) to
999.999999 [mm]
Sets the reference measured value for output.
Current
output value
4 (default value) to 20 [mA]
When the analog output destination is set to current,
sets the current to be output when the distance value is
measured.
Voltage
output value
-10 (default value) to 10 [V]
When the analog output destination is set to voltage,
sets the voltage to be output when the distance value
is measured.
Point2
Distance
value
-999.999999 to
3.000000 (default value) to
999.999999 [mm]
Sets the reference measured value for output.
Current
output value
4 (default value) to 20 [mA]
When the analog output destination is set to current,
sets the current to be output when the distance value is
measured.
Voltage
output value
-10 (default value) to 10 [V]
When the analog output destination is set to voltage,
sets the voltage to be output when the distance value
is measured.
The monitor focus can also be set with key operations on the Sensor Controller.
6
4
0
20
0
Meas
u
red
v
al
u
e
(mm)
O
u
tp
u
t c
u
rrent
(mA)
Point 1
Point 2
Important
Note
Summary of Contents for ZW-C1*AT
Page 17: ...ZW User s Manual 1 15 ...
Page 54: ...Installing the Sysmac Studio 52 ZW User s Manual MEMO ...
Page 74: ...Operating with Sensor Controller 72 ZW User s Manual MEMO ...
Page 120: ...Setting the System 118 ZW User s Manual MEMO ...
Page 138: ...Controll input signal with PC tool 136 ZW User s Manual MEMO ...
Page 262: ...No protocol Connection 260 ZW User s Manual MEMO ...
Page 271: ...8 Troubleshooting Troubleshooting 8 1 Error Messages 270 8 2 Troubleshooting 284 ...
Page 358: ...Connecting by No protocol Communications 356 ZW User s Manual MEMO ...
Page 449: ......