Connecting Parallel I/O
ZW User's Manual
343
Senso
r con
trol
ler ope
ra
ti
ons
9
Setting Operation at Judgment Output
Setting Operation at Judgment Output p.146
As an example, the following explains the procedure for setting the timer type to "1 SHOT" and the timer
duration to "10ms".
Operating procedure
Steps
Key operation
Display
Description
1 to 3
For moving to "JUDGE", see steps 1 to 3 in p.342.
4
Select the judgment output setting item.
HYS: Hysteresis width
TIMER: Timer mode
In this example, press the
/
keys, select "TIMER" and press the
key.
5
Select the timer mode.
OFF: Not set
OFF.DLY: Off Delay
ONDLY: On Delay
1SHOT: One Shot
Select "1SHOT" as the judgment output type.
The current setting value is displayed on the sub-display.
Press the
/
keys to enter the editing mode, and the sub-display
blinks.
Select "1SHOT" and press the
key.
6
Set the timer duration.
The current setting value is displayed on the sub-display.
Press
key to enter the editing mode, and the sub-display blinks.
To edit numerical values, use the
/
/
/
keys.
In this example, input "10", then press the
key.
7
Press and hold the
key for two seconds to enter the RUN mode.
Summary of Contents for ZW-C1*AT
Page 17: ...ZW User s Manual 1 15 ...
Page 54: ...Installing the Sysmac Studio 52 ZW User s Manual MEMO ...
Page 74: ...Operating with Sensor Controller 72 ZW User s Manual MEMO ...
Page 120: ...Setting the System 118 ZW User s Manual MEMO ...
Page 138: ...Controll input signal with PC tool 136 ZW User s Manual MEMO ...
Page 262: ...No protocol Connection 260 ZW User s Manual MEMO ...
Page 271: ...8 Troubleshooting Troubleshooting 8 1 Error Messages 270 8 2 Troubleshooting 284 ...
Page 358: ...Connecting by No protocol Communications 356 ZW User s Manual MEMO ...
Page 449: ......