107
Setting Touch Switches
Section 4-7
S
Noti Bit:
Specify the PC bit that is notified that the touch switch
has been pressed here (only when direct connection is
used).
S
No.:
Specify the number used to notify that a touch switch
has been pressed, or to control the touch switch on/off
(flashing) status (used only when direct connection is
not used).
S
Lamp Bit:
Specify the bit in the PC that controls the on/off (flash-
ing) status of the touch switch (used only when direct
connection is used).
S
Comment:
Input a memo here, for example one that indicates the
purpose of use.
S
Act Type:
Specify the effect of pressing the touch switch here.
When using an NT20M or NT600M, or an NT20S or
600S with Ver.5 direct connection, or using an NT612G
or NT610C and not using direct connection, or using
Ver.1 direct connection, setting is not possible and the
setting is fixed as “Moment”.
Moment:
The PC bit comes ON when the touch
switch is pressed and goes OFF when it is
released.
Altnat:
Each time the touch switch is pressed the
status of the PC bit (ON/OFF) is changed
to the opposite status.
Set:
The PC bit is switched ON when the touch
switch is pressed.
Rset:
The PC bit is switched OFF when the
touch switch is pressed.
Reference:
Specification of notify bits and input of I/O comments is possible by using either the
input notification window or the touch switch setting screen.
Summary of Contents for NT - SUPPORT TOOL 07-1995
Page 1: ...Cat No V028 E1 1 NT series Support Tool OPERATION MANUAL...
Page 2: ...i...
Page 3: ...ii...
Page 4: ...iii NT series Support Tool Operation Manual Produced July 1995...
Page 5: ...iv...
Page 19: ...xviii...
Page 25: ...6 IBM PC AT Preparations Section 1 2...
Page 37: ...18 Basic Operating Procedures Section 2 2...
Page 67: ...48 Scr list Screen Section 3 5...
Page 177: ...158 Editing Screen Data Section 4 15...
Page 193: ...174 Library Data Section 5 3...
Page 201: ...182 Printing Data Section 6 1...