6 Programless Communications
6 - 84
E5@D Digital Temperature Controllers Communications Manual (H225)
Check the values in the upload areas to see if they are the same as those that are given in
the following table. (It is not necessary to check address for which “---” is given in the Value
column.)
*
If the default settings are used and a sensor is not connected, the PV display on the E5CD will show an input
error (
s.err
) and the process value in the upload area will be 1320 (528 hex).
Changing E5CD Settings
(1) We will check the area that is used to change E5CD set values.
The area that is used to change the set value is called the download area.
D15 to D29 is the download area for the No. 0 Controller (E5CD), D45 to D59 is the
download area for the No. 1 Controller, and D75 to D89 is the download area for the No. 2
Controller.
With the default settings, the following parameters are set for the download areas.
No.0
No.1
No.2
Parameter
Value
D0
D30
D60
Response Flag (fixed)
0
D01
D31
D61
Communications Status (fixed)
Alternates between 0 and 1.
D02
D32
D62
Communications Monitor
---
D03
D33
D63
Status 1 (Upper Word)
---
D04
D34
D64
Status 1 (Lower Word)
---
D05
D35
D65
Status 2 (Upper Word)
---
D06
D36
D66
Decimal Point Monitor
---
D07
D37
D67
PV
PV*
D08
D38
D68
Internal Set Point
---
D09
D39
D69
Heater Current 1 Value Monitor
---
D10
D40
D70
MV Monitor (Heating)
---
D11
D41
D71
Spare
---
…
…
…
…
…
D14
D44
D74
Spare
---
No.0
No.1
No.2
Parameter
Value (E5CD default settings)
D15
D45
D75
Request Flag (fixed)
1 (0001 hex)
D16
D46
D76
Operation Command Code
(fixed)
0 (0000 hex)
D17
D47
D77
Set Point
0 (0000 hex)
D18
D48
D78
Proportional Band
80 (0050 hex)
D19
D49
D79
Integral Time
233 (00E9 hex)
D20
D50
D80
Derivative Time
40 (0028 hex)
D21
D51
D81
Alarm Value 1
0 (0000 hex)
D22
D52
D82
Alarm Value Upper Limit 1
0 (0000 hex)
D23
D53
D83
Alarm Value Lower Limit 1
0 (0000 hex)
D24
D54
D84
Alarm Value 2
0 (0000 hex)
No.0
No.1
No.2
Summary of Contents for E5 D Series
Page 2: ......
Page 20: ...18 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 28: ...1 Communications Methods 1 8 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 205: ...I 1 E5 D Digital Temperature Controllers Communications Manual H225 I Index ...
Page 208: ...I 4 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 209: ......