*1
P.END (program end output) can be set even when the program pattern is set to OFF, but the function will be disabled.
*2
You cannot set these values if you do not use the logic operation function.
Address
Parameter name
Setting (monitor) value
Level
Four-byt
e mode
Two-byt
e mode
0D24
2D12
Direct/Reverse Operation
H'00000000 (0): Reverse operation
H'00000001 (1): Direct operation
Initial setting
0D28
2D14
PID ON/OFF
H'00000000 (0): ON/OFF
H'00000001 (1): 2 PID control
0D2C
2D16
Program Pattern
H'00000000 (0): OFF
H'00000001 (1): STOP
H'00000002 (2): CONT
0D32
2D19
Minimum Output ON/OFF
Band
H'00000000 to H'000001F4 (0.0 to 50.0)
Advanced
function
setting
0D40
2D20
Adaptive Control
H'00000000 (0): Disabled
H'00000001 (1): Fixed
H'00000002 (2): Notification
H'00000003 (3): Automatic update
Initial Setting
0D42
2D21
Model Creation PV
Amplitude
H'00000000 to H'0000270F (0.00 to 99.99)
0D44
2D22
Model Creation MV
Amplitude
H'00000000 to H'000003E8 (0.0 to 100.0)
0D46
2D23
Model Creation ON Time
H'00000000 to H'0000270F (0 to 9999)
0D48
2D24
Model Creation OFF
Time
H'00000000 to H'0000270F (0 to 9999)
0E00
2E00
Transfer Output Type
H'00000000 (0): OFF
H'00000001 (1): Set point
H'00000002 (2): Set point during SP ramp
H'00000003 (3): PV
H'00000004 (4): MV (heating)
H'00000005 (5): MV (cooling)
0E02
2E01
Transfer Output Signal
H'00000000 (0): 4 to 20 mA
H'00000001 (1): 1 to 5 V
0E0C
2E06
Control Output 1 Assign-
ment
•
Control output 1 is a relay output or voltage output (for driving SSR): Advanced
function
setting
H'00000000 (0): Not assigned.
H'00000001 (1): Control output (heating)
H'00000002 (2): Control output (cooling)
H'00000003 (3): Alarm 1
H'00000004 (4): Alarm 2
H'00000005 (5): Alarm 3
H'00000006 (6): Alarm 4
H'00000007 (7): Heater alarm
H'00000008 (8): HB alarm
H'00000009 (9): HS alarm
H'0000000A (10): Input error
H'0000000B (11): Not assigned.
H'0000000C (12): Program end output
*1
H'0000000D (13): RUN output
H'0000000E (14): Integrated alarm
H'0000000F (15): Work bit 1
*2
H'00000010 (16): Work bit 2
*2
H'00000011 (17): Work bit 3
*2
H'00000012 (18): Work bit 4
*2
H'00000013 (19): Work bit 5
*2
H'00000014 (20): Work bit 6
*2
H'00000015 (21): Work bit 7
*2
H'00000016 (22): Work bit 8
*2
•
When control output 1 is a linear current output:
H'00000000 (0): Not assigned.
H'00000001 (1): Control output (heating)
H'00000002 (2): Control output (cooling)
0E0E
2E07
Control Output 2 Assign-
ment
Control output 2 is a relay output or voltage output (for driving SSR):
H'00000000 to H'0000006 (0 to 22)
Note: Same as for the Control Output 1 Assignment parameter.
Summary of Contents for E5 D Series
Page 2: ......
Page 20: ...18 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 28: ...1 Communications Methods 1 8 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 205: ...I 1 E5 D Digital Temperature Controllers Communications Manual H225 I Index ...
Page 208: ...I 4 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 209: ......