5 Communications Data for Modbus
5 - 12
E5@D Digital Temperature Controllers Communications Manual (H225)
0F1C
2F0E
Auxiliary Output 2 Open
in Alarm
H'00000000 (0): Close in alarm
H'00000001 (1): Open in alarm
Advanced
function
setting
0F1E
2F0F
Auxiliary Output 3 Open
in Alarm
H'00000000 (0): Close in alarm
H'00000001 (1): Open in alarm
0F20
2F10
Auxiliary Output 4 Open
in Alarm
H'00000000 (0): Close in alarm
H'00000001 (1): Open in alarm
0F22
2F11
Alarm 1 ON delay
H'00000000 to H'000003E7 (0 to 999)
0F24
2F12
Alarm 2 ON delay
H'00000000 to H'000003E7 (0 to 999)
0F26
2F13
Alarm 3 ON delay
H'00000000 to H'000003E7 (0 to 999)
0F28
2F14
Alarm 4 ON delay
H'00000000 to H'000003E7 (0 to 999)
0F2A
2F15
Alarm 1 OFF delay
H'00000000 to H'000003E7 (0 to 999)
0F2C
2F16
Alarm 2 OFF delay
H'00000000 to H'000003E7 (0 to 999)
0F2E
2F17
Alarm 3 OFF delay
H'00000000 to H'000003E7 (0 to 999)
0F30
2F18
Alarm 4 OFF delay
H'00000000 to H'000003E7 (0 to 999)
1000
3000
PV/SP No. 1 Display
Selection
H'00000000 (0):Nothing displayed.
H'00000001 (1):PV/SP
H'00000002 (2):PV
H'00000003 (3):PV/SP (character display)
H'00000004 (4): PV/SP/MV (heating)
H'00000005 (5):PV/SP/Multi-SP No.
H'00000006 (6):PV/SP/Soak time remain
H'00000007 (7):PV/SP/Ramp SP
H'00000008 (8):PV/SP/Alarm value 1
H'00000009 (9):PV/SP/MV (cooling)
1006
3003
Automatic Display Return
Time
H'00000000 (0): OFF
H'00000001 to H'00000063 (1 to 99)
1008
3004
Display Refresh Period
H'00000000 (0):OFF
H'00000001 (1): 0.25
H'00000002 (2): 0.5
H'00000003 (3): 1.0
1010
3008
PV/SP No. 2 Display
Selection
H'00000000 to H'00000009 (0 to 9)
Note: Same as PV/SP No. 1 Display Selection.
1014
300A
Display Brightness
H'00000001 to H'00000003 (1 to 3)
Advanced
function
setting
1018
300C
Move to Protect Level
Time
H'00000001 to H'0000001E (1 to 30)
1022
3011
PV Status Display
Function
H'00000000 (0): OFF
H'00000001 (1): Manual
H'00000002 (2): Stop
H'00000003 (3): Alarm 1
H'00000004 (4): Alarm 2
H'00000005 (5): Alarm 3
H'00000006 (6): Alarm 4
H'00000007 (7): Alarm 1 to 4 OR status
H'00000008 (8): Heater alarm
1024
3012
SV Status Display
Function
H'00000000 to H'00000008 (0 to 8)
Note: Same as for PV Status Display Function.
Address
Parameter name
Setting (monitor) value
Level
Four-byt
e mode
Two-byt
e mode
Summary of Contents for E5 D Series
Page 2: ......
Page 20: ...18 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 28: ...1 Communications Methods 1 8 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 205: ...I 1 E5 D Digital Temperature Controllers Communications Manual H225 I Index ...
Page 208: ...I 4 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 209: ......