5 Communications Data for Modbus
5 - 2
E5@D Digital Temperature Controllers Communications Manual (H225)
5-1
Variable Area (Setting Range) List
•
Four-byte Mode
One element uses 4 bytes of data (H'00000000 to H'FFFFFFFF), so specify two-element units.
Reading and writing in 4-byte units is executed by specifying an even address and specifying the
number of elements in multiples of 2.
•
Two-byte Mode
One element uses 2 bytes of data (H'0000 to H'FFFF), so specify one-element units. Reading and
writing in 2-byte data units is executed by specifying 1-element units.
The following table lists the variable area. Items expressed in hexadecimal in the "Setting (monitor)
value" column are the setting range in the Modbus specifications. Values in parentheses "()" are the
actual setting range.
When there is a section reference for a setting item, refer to that reference for details.
Address
Parameter name
Setting (monitor) value
Level
Four-byte
mode
Two-byt
e mode
0000
2000
PV
Temperature: Use the specified range for each sensor.
Analog: Scaling lower limit
−
5% FS to Scaling upper limit + 5% FS
Operation
0002
2001
Status 1
*1*2
Refer to
5-2 Status
for details.
0004
2002
Internal Set Point
*1
SP lower limit to SP upper limit
0006
2003
Heater Current 1 Value
Monitor
H'00000000 to H'00000226 (0.0 to 55.0)
0008
2004
MV Monitor (Heating)
Standard:
H'FFFFFFCE to H'0000041A (
−
5.0 to 105.0)
Heating and cooling:
H'00000000 to H'0000041A (0.0 to 105.0)
000A
2005
MV Monitor (Cooling)
H'00000000 to H'0000041A (0.0 to 105.0)
0106
2103
Set Point
SP lower limit to SP upper limit
0108
2104
Alarm Value 1
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
010A
2105
Alarm Value Upper Limit
1
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
010C
2106
Alarm Value Lower Limit
1
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
010E
2107
Alarm Value 2
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
0110
2108
Alarm Value Upper Limit
2
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
0112
2109
Alarm Value Lower Limit
2
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
0404
2402
PV
Temperature: Use the specified range for each sensor.
Analog: Scaling lower limit
−
5% FS to Scaling upper limit + 5% FS
0406
2403
Internal Set Point
*1
SP lower limit to SP upper limit
0408
2404
Multi-SP No. Monitor
H'00000000 to H'00000007 (0 to 7)
040C
2406
Status 1
*1*2
Refer to
5-2 Status
for details.
040E
2407
Status 1
*3
Refer to
5-2 Status
for details.
0410
2408
Status 2
*1*2
Refer to
5-2 Status
for details.
0412
2409
Status 2
*1*3
Refer to
5-2 Status
for details.
0420
2410
Decimal Point Monitor
H'00000000 to H'00000003 (0 to 3)
0422
2411
Control Output 1 ON/OFF
Count Monitor
H'00000000 to H'0000270F (0 to 9999)
Advanced
function
setting
0424
2412
Control Output 2 ON/OFF
Count Monitor
H'00000000 to H'0000270F (0 to 9999)
*1
Not displayed on the Controller display.
*2
In 2-byte mode, the rightmost 16 bits are read.
*3
In 2-byte mode, the leftmost 16 bits are read.
Summary of Contents for E5 D Series
Page 2: ......
Page 20: ...18 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 28: ...1 Communications Methods 1 8 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 205: ...I 1 E5 D Digital Temperature Controllers Communications Manual H225 I Index ...
Page 208: ...I 4 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 209: ......