6 - 31
6 Programless Communications
E5@D Digital Temperature Controllers Communications Manual (H225)
6-4 C
onn
ectin
g t
o
CP-
series PLC
s
6
6-
4-5 Che
ckin
g Ope
ration
With the default settings, the following parameters are set for the download areas.
(2) We will initialize the download areas with the set values from the E5CD Controllers.
The download areas have not been initialized, so we will initialize them with the set values
from the E5CD Controllers. Double-click
D0015
(Request Flag) in the PLC Memory Win-
dow. The following dialog box is displayed. Enter 2 (Initialize Download Areas) and click the
OK
Button.
(3) We will confirm that the download areas have been initialized.
When initialization is completed, D0000 (Response Flag) will change to 1 (Normal End) and
D0015 (Request Flag) will automatically change to 1 (Enable Writing). Check the download
area to see if it has been initialized to the values given in the above table.
Confirm this for the No. 1 and No. 2 Controllers as well.
(4) We will change the set point for the No. 0 Controller.
Double-click
D0017
(Set Point) in the PLC Memory Window, enter 100 (64 hex) for the
value, and then click the
OK
Button. Confirm that D0000 (Request Flag) remains at 1
(Enable Writing) and that the SV Display on the No. 0 Controller changes to 100.
Confirm this for the No. 1 and No. 2 Controllers as well.
No.0
No.1
No.2
Parameter
Value (E5CD default settings)
D0015
D0045
D0075
Request Flag (fixed)
1 (0001 hex)
D0016
D0046
D0076
Operation Command Code (fixed)
0 (0000 hex)
D0017
D0047
D0077
Set Point
0 (0000 hex)
D0018
D0048
D0078
Proportional Band
80 (0050 hex)
D0019
D0049
D0079
Integral Time
233 (00E9 hex)
D0020
D0050
D0080
Derivative Time
40 (0028 hex)
D0021
D0051
D0081
Alarm Value 1
0 (0000 hex)
D0022
D0052
D0082
Alarm Value Upper Limit 1
0 (0000 hex)
D0023
D0053
D0083
Alarm Value Lower Limit 1
0 (0000 hex)
D0024
D0054
D0084
Alarm Value 2
0 (0000 hex)
D0025
D0055
D0085
Alarm Value Upper Limit 2
0 (0000 hex)
D0026
D0056
D0086
Alarm Value Lower Limit 2
0 (0000 hex)
D0027
D0057
D0087
Heater Burnout Detection 1
0 (0000 hex)
D0028
D0058
D0088
Process Value Input Shift
0 (0000 hex)
D0029
D0059
D0089
SP Ramp Set Value
0 (0000 hex)
Summary of Contents for E5 D Series
Page 2: ......
Page 20: ...18 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 28: ...1 Communications Methods 1 8 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 205: ...I 1 E5 D Digital Temperature Controllers Communications Manual H225 I Index ...
Page 208: ...I 4 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 209: ......