4 - 15
4 Modbus Communications Procedure
E5@D Digital Temperature Controllers Communications Manual (H225)
4-4
Detail
ed Desc
rip
tio
n o
f th
e Fu
n
ct
ion
s
4
4-
4-4 Echoback
Test
Command Frame
Response Frame
Note: When the command is executed normally, the response returns the same data sent in the command.
(1) Test Data
Enter any 2-byte hexadecimal data.
(2) Response Code
(3) Example Command and Response
The following example shows the command/response for an Echoback Test command.
(In this case, the test data is H'1234.)
(In this case, the slave address is H'01.)
4-4-4 Echoback Test
Function code
Error
code
Name
Description
H
'
88
H
'
03
Variable data error
A different value (not H
'
00, H
'
00) was
returned.
H
'
08
---
Normal completion
No errors were found.
CRC-16
1
2
2
1
H'08
H'00
H'00
Test data
2 bytes
Slave
address
Function
code
Fixed data
CRC-16
1
2
2
1
H'08
H'00
H'00
Test data
2 bytes
Slave
address
Function
code
Fixed data
01
08
00 00
01
08
00 00
12 34
12 34
ED 7C(CRC-16)
ED 7C(CRC-16)
Command:
Response:
Summary of Contents for E5 D Series
Page 2: ......
Page 20: ...18 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 28: ...1 Communications Methods 1 8 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 205: ...I 1 E5 D Digital Temperature Controllers Communications Manual H225 I Index ...
Page 208: ...I 4 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 209: ......