5 - 15
5 Communications Data for Modbus
E5@D Digital Temperature Controllers Communications Manual (H225)
5
-1 Variab
le Area (Set
tin
g Ran
g
e)
List
5
Address
Parameter name
Setting (monitor) value
Level
Four-byt
e mode
Two-byt
e mode
1300
3300
Operation after Power
ON
H'00000000 (0): Continue
H'00000001 (1): STOP
H'00000002 (2): Manual*
Initial setting
130A
3305
Cold Junction
Compensation Method
H'00000000 (0): OFF
H'00000001 (1): ON
Advanced
function
setting
1312
3309
Integral/Derivative Time
Unit
H'00000000 (0): 1 s
H'00000001 (1): 0.1 s
1314
330A
α
H'00000000 to H'00000064 (0.00 to 1.00)
1318
330C
Manual Output Method
H'00000000 (0): HOLD
H'00000001 (1): INIT
131A
330D
Manual MV Initial Value
Standard control:
H'FFFFFFCE to H'0000041A (
−
5.0 to 105.0)
Heating and cooling control:
H'FFFFFBE6 to H'0000041A (
−
105.0 to 105.0)
131E
330F
AT Calculated Gain
H'00000001 to H'00000064 (0.1 to 10.0)
1320
3310
AT Hysteresis
H'00000001 to H'0000270F (0.1 to 999.9 for temperature input)
H'00000001 to H'000003E7 (0.01 to 9.99 for analog input)
1322
3311
Limit Cycle MV Amplitude H'00000032 to H'000001F4 (5.0 to 50.0)
1328
3314
Heater Burnout Latch
H'00000000 (0): OFF
H'00000001 (1): ON
132A
3315
Heater Burnout
Hysteresis
H'00000001 to H'000001F4 (0.1 to 50.0)
132C
3316
HS Alarm Latch
H'00000000 (0): OFF
H'00000001 (1): ON
132E
3317
HS Alarm Hysteresis
H'00000001 to H'000001F4 (0.1 to 50.0)
1336
331B
Number of Multi-SP
Points
H'00000001 (1): OFF
H'00000002 to H'00000008 (2 to 8)
1338
331C
HB ON/OFF
H'00000000 (0): OFF
H'00000001 (1): ON
133C
331E
Integrated Alarm
Assignment
H'00000000 to H'0000007F (0 to 127)
1344
3322
RT
H'00000000 (0): OFF
H'00000001 (1): ON
1346
3323
HS Alarm Use
H'00000000 (0): OFF
H'00000001 (1): ON
1348
3324
LBA Detection Time
H'00000000 to H'0000270F (0 to 9999)
134A
3325
LBA Level
H'00000001 to H'0000270F
(0.1 to 999.9 for temperature input)
(0.01 to 99.99 for analog input)
134C
3326
LBA Band
H'00000000 to H'0000270F
(0.0 to 999.9 for temperature input)
(0.00 to 99.99 for analog input)
134E
3327
Soak Time Unit
H'00000000 (0): Minutes
H'00000001 (1): Hours
H'00000002 (2): Seconds
*
1350
3328
Alarm SP Selection
H'00000000 (0): Set point during SP ramp
H'00000001 (1): Set point
1356
332B
Manual MV Limit Enable
H'00000000 (0): OFF
H'00000001 (1): ON
135A
332D
PV Rate of Change
Calculation Period
H'00000001 to H'000003E7 (1 to 999)
135C
332E
Heating/Cooling Tuning
Method
H'00000000 (0): Same as heating control.
H'00000001 (1): Linear
H'00000002 (2): Air cooling
H'00000003 (3): Water cooling
136A
3335
LCT Cooling Output Min.
ON Time
H'00000001 to H'0000000A (0.1 to 1.0)
*
This setting cannot be selected when ON/OFF control is being used.
Summary of Contents for E5 D Series
Page 2: ......
Page 20: ...18 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 28: ...1 Communications Methods 1 8 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 205: ...I 1 E5 D Digital Temperature Controllers Communications Manual H225 I Index ...
Page 208: ...I 4 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 209: ......