5 Communications Data for Modbus
5 - 4
E5@D Digital Temperature Controllers Communications Manual (H225)
0710
2708
Control Period (Heating)
H'FFFFFFFE (
−
2): 0.1 s
H'FFFFFFFF (
−
1): 0.2 s
H'00000000 (0): 0.5 s
H'00000001 to H'00000063 (1 to 99)
Initial setting
0712
2709
Control Period (Cooling)
H'FFFFFFFE (
−
2): 0.1 s
H'FFFFFFFF (
−
1): 0.2 s
H'00000000 (0): 0.5 s
H'00000001 to H'00000063 (1 to 99)
0718
270C
SP Ramp Time Unit
H'00000000 (0): EU/second
H'00000001 (1): EU/minute
H'00000002 (2): EU/hour
Advanced
function
setting
071A
270D
SP Ramp Set Value
H'00000000 (0): OFF
H'00000001 to H'0000270F (1 to 9999)
Adjustment
071C
270E
SP Ramp Fall Value
H'FFFFFFFF (
−
1): Same (Same as SP Ramp Set Value.)
H'00000000 (0): OFF
H'00000001 to H'0000270F (1 to 9999)
071E
270F
MV at Stop
Standard control:
H'FFFFFFCE to H'0000041A (
−
5.0 to 105.0)
Heating and cooling control:
H'FFFFFBE6 to H'0000041A (
−
105.0 to 105.0)
0722
2711
MV at PV Error
0726
2713
MV Change Rate Limit
H'00000000 to H'000003E8 (0.0 to 100.0)
0730
2718
PV Input Slope
Coefficient
H'00000001 to H'0000270F (0.001 to 9.999)
0734
271A
Heater Current 1 Value
Monitor
H'00000000 to H'00000226 (0.0 to 55.0)
Operation
0736
271B
Heater Burnout Detection
1
H'00000000 to H'000001F4 (0.0 to 50.0)
Adjustment
0738
271C
Leakage Current 1
Monitor
H'00000000 to H'00000226 (0.0 to 55.0)
Operation
073A
271D
HS Alarm 1
H'00000000 to H'000001F4 (0.0 to 50.0)
Adjustment
0746
2723
Process Value Input Shift
H'FFFFF831 to H'0000270F (
−
199.9 to 999.9)
0748
2724
Heater Current 2 Value
Monitor
H'00000000 to H'00000226 (0.0 to 55.0)
Operation
074A
2725
Heater Burnout Detection
2
H'00000000 to H'000001F4 (0.0 to 50.0)
Adjustment
074C
2726
Leakage Current 2
Monitor
H'00000000 to H'00000226 (0.0 to 55.0)
Operation
074E
2727
HS Alarm 2
H'00000000 to H'000001F4 (0.0 to 50.0)
Adjustment
0750
2728
Soak Time Remain
H'00000000 to H'0000270F (0 to 9999)
Operation
Address
Parameter name
Setting (monitor) value
Level
Four-byte
mode
Two-byt
e mode
Summary of Contents for E5 D Series
Page 2: ......
Page 20: ...18 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 28: ...1 Communications Methods 1 8 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 205: ...I 1 E5 D Digital Temperature Controllers Communications Manual H225 I Index ...
Page 208: ...I 4 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 209: ......