(4) We will change the set point for the No. 0 Controller.
Double-click
D17
(Set Point) in the Device Memory Dialog Box, enter 100 (64 hex) for the
value, click the
Set
Button, and then click the
Close
Button. Confirm that D0 (Request Flag)
remains at 1 (Enable Writing) and that the SV Display on the No. 0 Controller changes to
100.
Confirm this for the No. 1 and No. 2 Controllers as well.
Stopping the E5CD Controllers
(1) We will run the No. 0 Controller.
Change the RUN/STOP parameter (
r-s
) in the operation level of the E5CD to RUN (
run
).
(2) We will switch the No. 0 Controller to STOP.
In the Device Memory Dialog Box, make sure that D15 (Request Flag) is 1 (Enable Writing)
and then double-click
D16
(Operation Command Code). Select the HEX Option, enter 0101
hex (STOP), click the
Set
Button, and then click the
Close
Button. D16 will change to 0, D0
(Response Flag) will remain at 1 (Enable Writing), and “STOP” will be displayed on the No.
0 Controller (E5CD). Confirm this for the No. 1 and No. 2 Controllers as well. For details on
other operation command codes, refer to
6-3-4 Operation Command Codes
.
Summary of Contents for E5 D Series
Page 2: ......
Page 20: ...18 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 28: ...1 Communications Methods 1 8 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 205: ...I 1 E5 D Digital Temperature Controllers Communications Manual H225 I Index ...
Page 208: ...I 4 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 209: ......