3 Communications Data for CompoWay/F
3 - 2
E5@D Digital Temperature Controllers Communications Manual (H225)
3-1
Variable Area (Setting Range) List
•
For communications using a variable type not enclosed in parentheses in the following table, the set
value is double-word data (8 digits). For communications using a variable type enclosed in
parentheses, the set value is single-word data (4 digits).
•
For example, variable type C0 is double-word data (8 digits), and variable type 80 is single-word data
(4 digits).
•
Items expressed in hexadecimal in the "Setting (monitor) value" column are the setting range for
CompoWay/F communications. The values in parentheses are the actual setting range. When there
is a section reference for a setting item, refer to that reference for details.
*1
Not displayed on the Controller display.
Variable
type
Address
Parameter name
Setting (monitor) value
Level
C0 (80)
0000
PV
Temperature: Use the specified range for each sensor.
Analog:
Scaling lower limit
−
5% FS to Scaling
upper limit +5% FS
Operation
C0 (80)
0001
Status 1
*1*2
Refer to
3-2 Status 1 and Status 2
for details.
C0 (80)
0002
Internal Set Point
*1
SP lower limit to SP upper limit
C0 (80)
0003
Heater Current 1
Value Monitor
H'00000000 to H'00000226 (0.0 to 55.0)
C0 (80)
0004
MV Monitor
(Heating)
Standard:
H'FFFFFFCE to H'0000041A
(
−
5.0 to 105.0)
Heating and cooling: H'00000000 to H'0000041A
(0.0 to 105.0)
C0 (80)
0005
MV Monitor
(Cooling)
H'00000000 to H'0000041A (0.0 to 105.0)
C0 (80)
0006
Heater Current 2
Value Monitor
H'00000000 to H'00000226 (0.0 to 55.0)
C0 (80)
0007
Leakage Current 1
Monitor
H'00000000 to H'00000226 (0.0 to 55.0)
C0 (80)
0008
Leakage Current 2
Monitor
H'00000000 to H'00000226 (0.0 to 55.0)
C0 (80)
0009
Soak Time Remain
H'00000000 to H'0000270F (0 to 9999)
C0 (80)
000C
Multi-SP No.
Monitor
H'00000000 to H'00000007 (0 to 7)
C0 (80)
000E
Decimal Point
Monitor
*1
H'00000000 to H'00000003 (0 to 3)
C0 (80)
000F
Control Output 1
ON/OFF Count
Monitor
H'00000000 to H'0000270F (0 to 9999)
Advanced
Function
Setting
C0 (80)
0010
Control Output 2
ON/OFF Count
Monitor
H'00000000 to H'0000270F (0 to 9999)
C0 (80)
0011
Status 2
*1*2
Refer to
3-2 Status 1 and Status 2
.
Operation
C0 (80)
0012
Status 1
*1*3
Refer to
3-2 Status 1 and Status 2
.
C0 (80)
0013
Status 2
*1*3
Refer to
3-2 Status 1 and Status 2
.
C0 (80)
001D
Power ON Time
Monitor
H'00000000 to H'0000270F (0 to 9999)
Advanced
Function
Setting
C0 (80)
001E
Ambient
Temperature
Monitor
When temperature unit is °C: H'FFFFFFE2 to
H'0000004B (-30 to 75)
When temperature unit is °F: H'0000000A to
H'000000AB (10 to 171)
Summary of Contents for E5 D Series
Page 2: ......
Page 20: ...18 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 28: ...1 Communications Methods 1 8 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 205: ...I 1 E5 D Digital Temperature Controllers Communications Manual H225 I Index ...
Page 208: ...I 4 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 209: ......