2 - 7
2 CompoWay/F Communications Procedures
E5@D Digital Temperature Controllers Communications Manual (H225)
2-2 Stru
cture o
f C
ommand
Tex
t
2
2-
2-4 Add
resses
The variable type is converted to 2-byte ASCII and loaded to the frame. The following table shows the
available variable types.
Note: Setup area 1 has no read-only parameters, so there is no variable type "C2."
An address is appended to each of the variable types. Express addresses in 2-byte hexadecimal and
append them for the specified access size. The address depends on the parameter. Refer to
3-1 Vari-
able Area (Setting Range) List
for details.
The number of elements is expressed in 2-byte hexadecimal. The range that can be specified for the
number of elements depends on the command. Refer to
2-3 Detailed Description of the Services
for
details.
Note: No commands will be accepted and no responses will be returned when a memory error (RAM error) has
occurred or the Controller is initializing (until the Controller recognizes the process value after the power is
turned ON).
Variable type
Description
C0/80
R/O (read only) parameter for setup area 0.
C1/81
R/W parameter for setup area 0.
C3/83
R/W parameter for setup area 1.
2-2-4
Addresses
2-2-5
Number of Elements
2-2-6
List of Services (Main Request Codes and Sub-Request Codes)
MRC
SRC
Name of service
Processing
01
01
Read Variable Area
This service reads from the variable
area.
01
02
Write Variable Area
This service writes to the variable area.
01
04
Composite Read from Variable Area
This service reads from the variable area
in the order specified by the parameters.
01
13
Composite Write to Variable Area
This service writes to the variable area in
the order specified by the parameters.
05
03
Read Controller Attributes
This service reads the model number
and communications buffer size.
06
01
Read Controller Status
This service reads the operating status.
08
01
Echoback Test
This service performs an echoback test.
30
05
Operation Command
This service performs operations such
as RUN/STOP, executing/stopping AT
(auto-tuning), and moving to Setup Area
1.
Summary of Contents for E5 D Series
Page 2: ......
Page 20: ...18 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 28: ...1 Communications Methods 1 8 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 205: ...I 1 E5 D Digital Temperature Controllers Communications Manual H225 I Index ...
Page 208: ...I 4 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 209: ......