6 Programless Communications
6 - 10
E5@D Digital Temperature Controllers Communications Manual (H225)
Note: If more than one E5
@
D Controller is connected to the same communications line, set the starting address to
the same value for all of them. The E5
@
D Controller with communications unit number 0 will use the words
that start from the specified starting address, the E5
@
D Controller with unit number 1 will use the words that
start from the specified starting address plus 30 words, and the E5
@
D Controller with unit number 2 will use
the words that start from the specified starting address plus 60 words
Communications Setting Level
Display condition: The Protocol Setting parameter must be set to
fins
,
mcp4
, or
fxp4
.
Note: 1 The First Address Upper Word and First Address Lower Word parameters together specify the first
address.
Example:
(1) If the first address of the PLC is 123456, set the First Address Upper Word parameter to
12 and the First Address Lower Word parameter to 3456 in the E5
@
D.
(2) If you use an area labeled with “*1,” convert the first address of the PLC (hexadecimal) to
a decimal number and set the decimal value in the E5
@
D.
If the first address of the PLC is 12345, set the First Address Upper Word parameter to 7
and the First Address Lower Word parameter to 4565 in the E5
@
D.
Address
Data in PLC memory
E5
@
D
Each E5
@
D
Controller is
allocated 30
words.
XXXX Response Flag
←
Communications Unit Number 0
+1 Communications Status
+2 Monitor Value 1
· · ·
+15 Request Flag
→
+16 Operation Command Code
+17 Set Value 1
· · ·
+30 Response Flag
←
No.1
+31 Communications Status
· · · · · ·
Parameter name
Displayed characters
Setting range
Default
Area
area
•
When Protocol Setting Parameter Is Set to FINS
0
0:
DM
1:
EM0
2:
EM1
3:
EM2
4:
EM3
5:
EM4
6:
EM5
7:
EM6
8:
EM7
9:
EM8
10: EM9
11: EMA
12: EMB
13: EMC
14: EMD
15: EME
16: EMF
17: EM10
18: EM11
19: EM12
20: EM13
21: EM14
22: EM15
23: EM16
24: EM17
25: EM18
•
When Protocol Setting Parameter Is Set to MCP4
0: D data registers
1: W link registers
*1
2: R file registers
3: ZR file registers
*1
4 to 25: D data registers
•
When Protocol Setting Parameter Is Set to FXP4
0: D data registers (DM
data memory registers)
1: None (W link registers)
*1
2: R expansion registers
(FM file registers)
3 to 25: Do not use.
Device names in parentheses are for Keyence
KV-series PLCs.
First Address Upper
Word
adrh
0 to 99
0
First Address Lower
Word
adrl
0 to 9999
0
Summary of Contents for E5 D Series
Page 2: ......
Page 20: ...18 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 28: ...1 Communications Methods 1 8 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 205: ...I 1 E5 D Digital Temperature Controllers Communications Manual H225 I Index ...
Page 208: ...I 4 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 209: ......