Address
Parameter name
Setting (monitor) value
Level
Four-byte
mode
Two-byt
e mode
1100
3100
Protocol Setting (See
note.)
H'00000000 (0): CompoWay/F
H'00000001 (1): Modbus
H'00000002 (2): Disabled
H'00000003 (3): Host Link (FINS)
H'00000004 (4): MC protocol (Format 4)
H'00000005 (5): Dedicated protocol (Format 4)
Communications
setting
1102
3101
Communications Unit No.
*
H'00000000 to H'00000063 (0 to 99)
1104
3102
Communications Baud
Rate *
H'00000003 (3): 9.6
H'00000004 (4): 19.2
H'00000005 (5): 38.4
H'00000006 (6): 57.6
H'00000007 (7): 115.2
1106
3103
Communications Data
Length *
H'00000007 (7): 7
H'00000008 (8): 8
1108
3104
Communications Stop
Bits *
H'00000001 (1): 1
H'00000002 (2): 2
110A
3105
Communications Parity *
H'00000000 (0): None
H'00000001 (1): Even
H'00000002 (2): Odd
110C
3106
Send Data Wait Time *
H'00000000 to H'00000063 (0 to 99)