2 CompoWay/F Communications Procedures
2 - 10
E5@D Digital Temperature Controllers Communications Manual (H225)
(4) Response Code
•
Normal Completion
•
Error Occurred
*1 For details on AT (auto-tuning), refer to the
E5
@
D Digital Temperature Controllers User's Manual
(Cat. No.
H224).
*2 For details on automatic filter adjustment, refer to the
E5
@
D Digital Temperature Controllers User's Manual
(Cat. No. H224).
(5) Precautions
•
Alarm Function
Even though alarms are not displayed on the Controller's display, they function normally in
communications.
Response code
Name
Description
0000
Normal completion
No errors were found.
Response code
Error name
Cause
1002
Command too short
The command is too short.
1101
Area type error
The variable type is wrong.
1103
Start address out-of-range error
Write start address is out of range.
1104
End address out-of-range error
The write end address (write start a
number of elements) exceeds the final address of
the variable area.
1003
Number of elements/data
mismatch
The number of data does not match the number of
elements.
1100
Parameter error
•
Bit position is not “00.”
•
The write data is out of the setting range.
3003
Read-only error
Variable type “C0” was written to.
2203
Operation error
•
The Communications Writing parameter is set to
“OFF” (disabled).
•
Attempted to write to a parameter in setup area
1 from setup area 0.
•
Attempted to write to a protect parameter from
other than the protect level.
•
AT (auto-tuning) was in progress. *1
•
Automatic filter adjustment is in progress. *2
•
Non-volatile memory error
Summary of Contents for E5 D Series
Page 2: ......
Page 20: ...18 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 28: ...1 Communications Methods 1 8 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 205: ...I 1 E5 D Digital Temperature Controllers Communications Manual H225 I Index ...
Page 208: ...I 4 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 209: ......