3 Communications Data for CompoWay/F
3 - 16
E5@D Digital Temperature Controllers Communications Manual (H225)
C3 (83)
0073
PV/SP No. 1 Display
Selection
H'00000000 (0): Nothing displayed.
H'00000001 (1): PV/SP
H'00000002 (2): PV
H'00000003 (3): PV/SP (character display)
H'00000004 (4): PV/SP/MV (heating)
H'00000005 (5): PV/SP/Multi-SP No.
H'00000006 (6): PV/SP/Soak time remain
H'00000007 (7): PV/SP/Internal SP (ramp SP)
H'00000008 (8): PV/SP/Alarm value 1
H'00000009 (9): PV/SP/MV (cooling)
Advanced
function
setting
C3 (83)
0076
PV Status Display
Function
H'00000000 (0): OFF
H'00000001 (1): Manual
H'00000002 (2): Stop
H'00000003 (3): Alarm 1
H'00000004 (4): Alarm 2
H'00000005 (5): Alarm 3
H'00000006 (6): Alarm 4
H'00000007 (7): Alarm 1 to 4 OR status
H'00000008 (8): Heater alarm
C3 (83)
0077
SV Status Display
Function
H'00000000 to H'00000008 (0 to 8)
Note: Same as for PV Status Display
Function
C3 (83)
0083
Display Refresh
Period
H'00000000 (0): OFF
H'00000001 (1): 0.25
H'00000002 (2): 0.5
H'00000003 (3): 1.0
C3 (83)
0084
Alarm 4 Type
H'00000000 to H'00000011 (0 to 17)
Note: Same settings as the Alarm 1 Type.
However, the LBA (loop burnout alarm)
cannot be set.
Initial setting
C3 (83)
0085
Event Input
Assignment 5
H'00000000 to H'0000000D (0 to 13)
Note: Same as for Event Input Assignment 1.
C3 (83)
0086
Event Input
Assignment 6
H'00000000 to H'0000000D (0 to 13)
Note: Same as for Event Input Assignment 1.
C3 (83)
0087
Auxiliary Output 4
Open in Alarm
H'00000000 (0): Close in alarm
H'00000001 (1): Open in alarm
Advanced
function setting
C3 (83)
0088
Alarm 4 Hysteresis
H'00000001 to H'0000270F
(0.1 to 999.9 for temperature input)
(0.01 to 99.99 for analog input)
Initial setting
C3 (83)
0089
Moving Average
Count
H'00000000 (0): OFF
H'00000001 (1): 2 times
H'00000002 (2): 4 times
H'00000003 (3): 8 times
H'00000004 (4): 16 times
H'00000005 (5): 32 times
Advanced
function setting
C3 (83)
008A
Alarm 4 Latch
H'00000000 (0): OFF
H'00000001 (1): ON
C3 (83)
008B
Alarm 4 ON delay
H'00000000 to H'000003E7 (0 to 999)
C3 (83)
008C
Alarm 4 OFF delay
H'00000000 to H'000003E7 (0 to 999)
C3 (83)
008E
Transfer Output
Signal
H'00000000 (0): 4 to 20 mA
H'00000001 (1): 1 to 5 V
Initial setting
Variable
type
Address
Parameter name
Setting (monitor) value
Level
Summary of Contents for E5 D Series
Page 2: ......
Page 20: ...18 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 28: ...1 Communications Methods 1 8 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 205: ...I 1 E5 D Digital Temperature Controllers Communications Manual H225 I Index ...
Page 208: ...I 4 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 209: ......