4 - 11
4 Modbus Communications Procedure
E5@D Digital Temperature Controllers Communications Manual (H225)
4-4
Detail
ed Desc
rip
tio
n o
f th
e Fu
n
ct
ion
s
4
4-
4-2 Var
iable Write, Multiple
z
Response Frame
Response Code
Name
Description
Slave address
The value from the command frame is entered as-is.
Function code
This is the received function code.
When the function ended normally, the function code is left as-is. When
an error occurred, the hexadecimal value of H'80 is added to the function
code to indicate that the response is an error response.
Example: Received function code = H'10
Function code in response frame when an error occurred =
H'90
Write start address
This is the received write start address.
Number of elements
This is the received number of elements.
CRC-16
This check code is calculated with the data from the slave address to the
end of the data.
For details on the CRC-16 calculation, refer to
CRC-16 Calculation
Example
in
4-1-1 Command Frame
on page 4-2.
Function code
Error code
Error name
Cause
H
'
90
H
'
02
Variable address
error
The write start address is incorrect.
H
'
03
Variable data error
•
The amount of data does not match the
number of elements.
•
The byte count is not 2 times the number
of elements.
•
The write data is out of the setting range.
H
'
04
Operation error
The Controller cannot write the data in its
present operating status.
The write data contents are not allowed in
the present operation mode.
•
The Communications Writing parameter is
set to "OFF" (disabled).
•
Attempted to write to a parameter in setup
area 1 from setup area 0.
•
Attempted to write to a protect parameter
from other than the protect level.
•
AT execution is in progress.
•
Automatic filter adjustment is in progress.
H
'
10
---
Normal completion
No errors were found.
CRC-16
1
2
2
1
H’ 10
Number of
Elements
2 bytes
Slave
address
Function
code
Write start address
Summary of Contents for E5 D Series
Page 2: ......
Page 20: ...18 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 28: ...1 Communications Methods 1 8 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 205: ...I 1 E5 D Digital Temperature Controllers Communications Manual H225 I Index ...
Page 208: ...I 4 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 209: ......