6 Programless Communications
6 - 90
E5@D Digital Temperature Controllers Communications Manual (H225)
z
Changing E5CD Settings
(1) We will check the area that is used to change E5CD set values.
The area that is used to change the set value is called the download area.
DM15 to DM29 is the download area for the No. 0 Controller (E5CD), DM45 to DM59 is the
download area for the No. 1 Controller, and DM75 to DM89 is the download area for the
No. 2 Controller.
With the default settings, the following parameters are set for the download areas.
(2) We will initialize the download areas with the set values from the E5CD Controllers.
The download areas have not been initialized, so we will initialize them with the set values
from the E5CD Controllers.
Double-click
DM15
(Request Flag) on the Batch Monitor Dialog Box, enter 2 (Initialize
Download Areas), and press the
Enter
Key.
(3) We will confirm that the download areas have been initialized.
When initialization is completed, DM0 (Response Flag) will change to 1 (Normal End) and
DM15 (Request Flag) will automatically change to 1 (Enable Writing). Check the download
area to see if it has been initialized to the values given in the above table.
Confirm this for the No. 1 and No. 2 Controllers as well.
(4) We will change the set point for the No. 0 Controller.
Double-click
DM17
(Set Point) on the Batch Monitor Dialog Box, enter 100 (64 hex) as the
value, and press the
Enter
Key. Confirm that DM0 (Request Flag) remains at 1 (Enable
Writing) and that the SV Display on the No. 0 Controller changes to 100.
Confirm this for the No. 1 and No. 2 Controllers as well.
z
Stopping the E5CD Controllers
(1) We will run the No. 0 Controller.
Change the RUN/STOP parameter (
r-s
) in the operation level of the E5CD to RUN (
run
).
No.0
No.1
No.2
Parameter
Value (E5CD default settings)
DM15
DM45
DM75
Request Flag (fixed)
1 (0001 hex)
DM16
DM46
DM76
Operation Command Code (fixed)
0 (0000 hex)
DM17
DM47
DM77
Set Point
0 (0000 hex)
DM18
DM48
DM78
Proportional Band
80 (0050 hex)
DM19
DM49
DM79
Integral Time
233 (00E9 hex)
DM20
DM50
DM80
Derivative Time
40 (0028 hex)
DM21
DM51
DM81
Alarm Value 1
0 (0000 hex)
DM22
DM52
DM82
Alarm Value Upper Limit 1
0 (0000 hex)
DM23
DM53
DM83
Alarm Value Lower Limit 1
0 (0000 hex)
DM24
DM54
DM84
Alarm Value 2
0 (0000 hex)
DM25
DM55
DM85
Alarm Value Upper Limit 2
0 (0000 hex)
DM26
DM56
DM86
Alarm Value Lower Limit 2
0 (0000 hex)
DM27
DM57
DM87
Heater Burnout Detection 1
0 (0000 hex)
DM28
DM58
DM88
Process Value Input Shift
0 (0000 hex)
DM29
DM59
DM89
SP Ramp Set Value
0 (0000 hex)
Summary of Contents for E5 D Series
Page 2: ......
Page 20: ...18 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 28: ...1 Communications Methods 1 8 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 205: ...I 1 E5 D Digital Temperature Controllers Communications Manual H225 I Index ...
Page 208: ...I 4 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 209: ......