6 Programless Communications
6 - 20
E5@D Digital Temperature Controllers Communications Manual (H225)
Programless communications start operating after the power supply is turned ON or after the E5
@
D is
reset. They stop operating when the initial setting level is entered.
The following table gives the operation command codes that can be set.
For details on operation commands, refer to
2-3-8 Operation Command
.
You can check the operation of programless communications in the Communications Status in the
upload area.
The value of the Communications Status changes between 0 and 1 each time the upload area is
updated.
6-3-3
Range of Operation for Programless Communications
Levels
Programless communications
Operation level, adjustment level, manual control level,
monitor/setting item level, and protect level
Setting area 0
Operates
Initial setting level, communications setting level, advanced
function setting level, and calibration level
Setting area 1
Stops
6-3-4
Operation Command Codes
Operation command
Operation command code
Switch
RUN/STOP
0100
RUN
0101
STOP
Multi-SP
0200
SP 0
0201
SP 1
0202
SP 2
0203
SP 3
0204
SP 4
0205
SP 5
0206
SP 6
0207
SP 7
AT Execute/Cancel
0300
AT Cancel
0301
100% AT Execute
0302
40% AT Execute
Write Mode
0400
Backup Mode
0401
RAM Write Mode
Save RAM Data
0500
Save RAM Data
Software Reset
0600
Software Reset
Auto/Manual
0900
Automatic Mode
0901
Manual Mode
Alarm Latch Cancel
0C00
Alarm 1 Latch Cancel
0C01
Alarm 2 Latch Cancel
0C02
Alarm 3 Latch Cancel
0C03
Heater Burnout Latch Cancel
0C04
HS Alarm Latch Cancel
0C05
Alarm 4 Latch Cancel
0C0F
All Latch Cancel
Invert Direct/Reverse
Operation
0E00
Do Not Invert
0E01
Invert
PID Update (adaptive control)
0F00
PID Update
Program Start
1100
Reset
1101
Start
Automatic Filter Adjustment
1200
OFF
1201
ON
6-3-5
Confirming Operation of Programless Communications
Summary of Contents for E5 D Series
Page 2: ......
Page 20: ...18 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 28: ...1 Communications Methods 1 8 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 205: ...I 1 E5 D Digital Temperature Controllers Communications Manual H225 I Index ...
Page 208: ...I 4 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 209: ......