Writing Undisplayed Parameters
It is possible to write the parameters that are not displayed due to display settings as well as the
parameters that are never displayed in the Controller.
•
Example Command and Response
The following example shows the command/response when writing the Alarm Value Upper Limit 1
and Alarm Value Lower Limit 1 parameters.
(In this case, the slave address is H'01.)
Four-byte Mode
Alarm Value Upper Limit 1
•
Address: H'010A; Write data: H'000003E8 (when 1000)
Alarm Value Lower Limit 1
•
Address: H'010C; Write data: H'FFFFFC18 (when
−
1000)
Two-byte Mode
Alarm Value Upper Limit 1
•
Address: H'2105; Write data: H'03E8 (when 1000)
Alarm Value Lower Limit 1
•
Address: H'2106; Write data: H' FC18 (when
−
1000)
This function performs operations such as writing to the variable area (single) and operation commands
(communications writing, RUN/STOP, multi-SP, AT execute/cancel, write mode, save RAM data, soft-
ware reset, move to setup area 1, move to protect level, auto/manual switch, initialize settings, alarm
latch cancel, invert direct/reverse operation, PID update (adaptive control), program start, and auto-
matic filter adjustment.)
Writing is enabled in only the 2-byte mode.
Command Frame
Response Frame
(1) Write variable address
Specify the address of the setting data that is to be written. For details on addresses, refer
to
Section 5 Modbus Communications Procedure
.
For an operation command, specify 0000 or FFFF.
4-4-3 Variable Write, Single/Operation Command
01
10
01 0A
01
10
01 0A
00 04
00 04
E0 34(CRC-16)
08
00 00 03 E8
FF FF FC 18
8D E9(CRC-16)
Command:
Response:
01
10
21 05
01
10
21 05
00 02
00 02
5B F5(CRC-16)
04
03 E8
FC 18
66 BB(CRC-16)
Command:
Response:
CRC-16
1
2
2
1
H'06
Write data
2 bytes
Slave
address
Function
code
Write variable
address
CRC-16
1
2
2
1
H'06
Write data
2 bytes
Slave
address
Function
code
Write variable
address
Summary of Contents for E5 D Series
Page 2: ......
Page 20: ...18 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 28: ...1 Communications Methods 1 8 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 205: ...I 1 E5 D Digital Temperature Controllers Communications Manual H225 I Index ...
Page 208: ...I 4 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 209: ......