5 - 5
5 Communications Data for Modbus
E5@D Digital Temperature Controllers Communications Manual (H225)
5
-1 Variab
le Area (Set
tin
g Ran
g
e)
List
5
0752
2729
Soak Time
H'00000001 to H'0000270F (1 to 9999)
Adjustment
0754
272A
Wait Band
H'00000000 (0): OFF
H'00000001 to H'0000270F
(0.1 to 999.9 for Temperature input)
(0.01 to 99.99 for Analog input)
0760
2730
SP Response
Proportional Band
H'00000001 to H'0000270F (0.1 to 999.9)
0762
2731
SP Response Integral
Time
H'00000000 to H'0000270F
(0 to 9999: Integral/derivative time unit is 1 s.)
(0.0 to 999.9: Integral/derivative time unit is 0.1 s.)
0764
2732
SP Response Derivative
Time
H'00000000 to H'0000270F
(0 to 9999: Integral/derivative time unit is 1 s.)
(0.0 to 999.9: Integral/derivative time unit is 0.1 s.)
0766
2733
SP Response Coefficient
Number
H'00000000 to H'0000270F (0 to 9999)
0768
2734
Disturbance Proportional
Band
H'00000001 to H'0000270F (0.1 to 999.9)
076A
2735
Disturbance Integral Time H'00000000 to H'0000270F
(0 to 9999: Integral/derivative time unit is 1 s.)
(0.0 to 999.9: Integral/derivative time unit is 0.1 s.)
076C
2736
Disturbance Derivative
Time
H'00000000 to H'0000270F
(0 to 9999: Integral/derivative time unit is 1 s.)
(0.0 to 999.9: Integral/derivative time unit is 0.1 s.)
076E
2737
Input Digital Filter
H'00000000 to H'0000270F (0.0 to 999.9)
0770
2738
Water-cooling Output
Adjustment
H'00000000 (0): OFF
H'00000001 (1): ON
0772
2739
Water-cooling
Proportional Band
Increase Threshold
Water-cooling Proportional Band Decrease Thr 0.1 to
H'000007D0 (200.0)
0774
273A
Water-cooling
Proportional Band
Decrease Threshold
H'00000000 (0): OFF
H'00000001 (0.1) to Water-cooling Proportional Band Increase
Threshold - 0.1
0800
2800
Input Digital Filter
H'00000000 to H'0000270F (0.0 to 999.9)
0808
2804
Moving Average Count
H'00000000 (0): OFF
H'00000001 (1): 2 times
H'00000002 (2): 4 times
H'00000003 (3): 8 times
H'00000004 (4): 16 times
H'00000005 (5): 32 times
Advanced
function
setting
Address
Parameter name
Setting (monitor) value
Level
Four-byte
mode
Two-byt
e mode
Summary of Contents for E5 D Series
Page 2: ......
Page 20: ...18 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 28: ...1 Communications Methods 1 8 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 205: ...I 1 E5 D Digital Temperature Controllers Communications Manual H225 I Index ...
Page 208: ...I 4 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 209: ......