6-10 Connecting to MELSEC iQ-R-series
PLCs
The following configuration is used as an example in giving the setup and application procedures for
programless communications.
•
All of the E5CD Controllers must be the same model. (Copying parameter settings is not possible if
the models are different.)
•
D0 to D89 are used in the PLC memory. The default E5CD parameter allocations are used.
•
A USB A/mini-B cable is used.
Note: Refer to the GX Works3 Installation Instructions (BCN-P5999 ) for information on installing the GX Works3
and to the GX Works3 Operating Manual (SH-081214) for information on installing the USB driver.
The application procedure is given below.
6-10-1 Configuration and Procedure
E5CD
No.0
E5CD
No.1
E5CD
No.2
RS-485
USB port
GX Works3
Support Software
Computer
IBM PC/AT or compatible
Commercially
available USB cable
USB connector
R
CPU
RJ71C24
START
Wiring
Wire the RJ71C24 to the E5
D Controllers.
E5
D Controller Setup
Set up programless communications in the E5CD Controllers.
Checking Operation
Use GX Works3 to confirm that programless communications are operating.
PLC Setup
Use GX Works3 to set up communications on the RJ71C24 to enable
communicating with the E5CD Controllers.
END
Summary of Contents for E5 D Series
Page 2: ......
Page 20: ...18 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 28: ...1 Communications Methods 1 8 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 205: ...I 1 E5 D Digital Temperature Controllers Communications Manual H225 I Index ...
Page 208: ...I 4 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 209: ......