6 Programless Communications
E5@D Digital Temperature Controllers Communications Manual (H225)
6-9 C
on
necti
n
g t
o
MEL
SEC
-FX-
series PLC
s
6
6-
9-2 Wiring
Set the terminating resistance switch on the front panel of the FX3U-485ADP-MB to 110
Ω
.
Wire the FX3U-485ADP-MB to the E5CD Controllers as shown below.
Note: 1 Use a terminating resistance of at least 54
Ω
.
2 The maximum transmission distance is 500 m.
3 For wiring methods, refer to
4.5.1 One-pair wiring
under
D.Computer Link
in the
FX Series User’s Manual,
Data Communication Edition
(JY997D16901)
.
Set up communications on the FX3U-485ADP-MB to enable communicating with the E5CD Controllers.
PLC operation will stop and the power supply will be cycled during the setup procedure. Make sure that
this will not create any problems in the controlled system.
Connecting to the PLC
(1) Connect the computer to the FX-series CPU Module with a USB cable and then start
GX Works2.
(2) Select
Online
−
Read from PLC
from the menu bar.
(3) Select
FXCPU
, and then click the OK Button.
6-9-2
Wiring
6-9-3
PLC Setup
330
Ω
OPEN
110
Ω
FX3U-485ADP-MB
SDA
SDB
RDA
RDB
SG
Shield
Shield
Shield
13
14
E5CD
No.0
E5CD
No.1
E5CD
No.2
B(+)
A(
−
)
13
14
B(+)
A(
−
)
13
14
B(+)
A(
−
)
120
Ω
(1/2 W)
terminating resistance
Summary of Contents for E5 D Series
Page 2: ......
Page 20: ...18 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 28: ...1 Communications Methods 1 8 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 205: ...I 1 E5 D Digital Temperature Controllers Communications Manual H225 I Index ...
Page 208: ...I 4 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 209: ......