1 - 5
1 Communications Methods
E5@D Digital Temperature Controllers Communications Manual (H225)
1-1 Overview of
Co
mmu
nica
-
tio
n
s Met
hod
s
1
1-
1-6
Communications Paramete
rs
The E5
@
D's communications specifications are set in the communications setting level. These param-
eters are set on the E5
@
D's front panel. The following table shows the communications parameters and
their setting ranges.
Highlighted values indicate default settings.
*1
The setting parameters for programless communications are displayed when the protocol selection is set to
Host Link (FINS), MC Protocol (Format 4), or Dedicated Protocol (Format 4). Refer to
Section 6 Programless
Communications
for details.
*2
When the Protocol Setting parameter is set to Modbus, the communications data length must be 8 bits, and
the communications stop bits must be 1 bit by setting the communications parity to Even/Odd or it must be 2
bits by setting the parity to None. These two parameters are not displayed on the Controller's display.
1-1-6
Communications Parameters
Item
Code
Settings
Set Values
Communications protocol
setting *1
psel
CompoWay/F, Modbus, None,
Host Link (FINS), MC Protocol
(Format 4), or Dedicated Protocol
(Format 4)
cwf
/
mod
/
none
/
fins
/
mcp4
/
fxp4
Communications unit number
u-no
0 to 99
0, 1 to 99
Communications baud rate
bps
9.6/19.2/38. 4/57.6/115.2 (kbit/s)
9.6/19.2 /38.4/57.6/115.2 (kbit/s)
Communications data length *2
len
7/8 (bit)
7/8 (bit)
Communications stop bits *2
sbit
1/2
1/2
Communications parity
prty
None, Even, Odd
none
/
eVen
/
odd
Send data wait time
sdwt
0 to 99
0 to 99 ms, default time: 20 ms
Write mode
ramm
Backup mode, RAM write mode
bkup
/
ram
Summary of Contents for E5 D Series
Page 2: ......
Page 20: ...18 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 28: ...1 Communications Methods 1 8 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 205: ...I 1 E5 D Digital Temperature Controllers Communications Manual H225 I Index ...