5 Communications Data for Modbus
5 - 10
E5@D Digital Temperature Controllers Communications Manual (H225)
Address
Parameter name
Setting (monitor) value
Level
Four-byte
mode
Two-byt
e mode
0E14
2E0A
Event Input Assignment 1
H'00000000 (0): None
H'00000001 (1): RUN/STOP
H'00000002 (2): Auto/Manual Switch
H'00000003 (3): Program Start
*1
H'00000004 (4): Direct/Reverse Operation
H'00000005 (5): None
H'00000006 (6): 100% AT Execute/Cancel
H'00000007 (7): 40% AT Execute/Cancel
H'00000008 (8): Setting Change Enable/Disable
H'00000009 (9): Communications Writing Enable/Disable
*2
H'0000000A (10): Alarm Latch Cancel
H'0000000B (11): Multi-SP No. Switch, Bit 0
H'0000000C (12): Multi-SP No. Switch, Bit 1
H'0000000D (13): Multi-SP No. Switch, Bit 2
H'0000000E (14): STOP/RUN
H'0000000F (15): PID Update (Adaptive Control)
H'00000010 (16): Automatic Filter Adjustment
H'00000011 (17): Water-cooling Output Adjustment
Initial setting
0E16
2E0B
Event Input Assignment 2
H'00000000 to H'00000011 (0 to 17)
Note: Same as for Event Input Assignment 1.
0E18
2E0C
Event Input Assignment 3
H'00000000 to H'00000011 (0 to 17)
Note: Same as for Event Input Assignment 1.
0E1A
2E0D
Event Input Assignment 4
H'00000000 to H'00000011 (0 to 17)
Note: Same as for Event Input Assignment 1.
0E1C
2E0E
Event Input Assignment 5
H'00000000 to H'0000000D (0 to 13)
Note: Same as for Event Input Assignment 1.
0E1E
2E0F
Event Input Assignment 6
H'00000000 to H'0000000D (0 to 13)
Note: Same as for Event Input Assignment 1.
0E20
2E10
Auxiliary Output 1
Assignment
H'00000000 (0): Not assigned.
H'00000001 (1): Control output (heating)
H'00000002 (2): Control output (cooling)
H'00000003 (3): Alarm 1
H'00000004 (4): Alarm 2
H'00000005 (5): Alarm 3
H'00000006 (6): Alarm 4
H'00000007 (7): Heater alarm
H'00000008 (8): HB alarm
H'00000009 (9): HS alarm
H'0000000A (10): Input error
H'0000000B (11): Not assigned.
H'0000000C (12): Program end output
*3
H'0000000D (13): RUN output
H'0000000E (14): Integrated alarm
H'0000000F (15): Work bit 1
*4
H'00000010 (16): Work bit 2
*4
H'00000011 (17): Work bit 3
*4
H'00000012 (18): Work bit 4
*4
H'00000013 (19): Work bit 5
*4
H'00000014 (20): Work bit 6
*4
H'00000015 (21): Work bit 7
*4
H'00000016 (22): Work bit 8
*4
Advanced
function
setting
0E22
2E11
Auxiliary Output 2
Assignment
H'00000000 to H'00000016 (0 to 22)
Note: Same as for the Auxiliary Output 1 Assignment parameter.
0E24
2E12
Auxiliary Output 3
Assignment
H'00000000 to H'00000016 (0 to 22)
Note: Same as for the Auxiliary Output 1 Assignment parameter.
0E26
2E13
Auxiliary Output 4
Assignment
H'00000000 to H'00000016 (0 to 22)
Note: Same as for the Auxiliary Output 1 Assignment parameter.
0E28
2E14
Transfer Output Upper Limit
H'FFFFF831 to H'0000270F (
Ŧ
1999 to 9999)
*5
Initial setting
0E2A
2E15
Transfer Output Lower Limit
H'FFFFF831 to H'0000270F (
Ŧ
1999 to 9999)
*5
*1
PRST (program start) can be set even when the program pattern is set to OFF, but the function will be disabled.
*2
Selection is possible only if external communications is supported.
*3
P.END (program end output) can be set even when the program pattern is set to OFF, but the function will be disabled.
*4
You cannot set these values if you do not use the logic operation function.
*5
The setting (monitor) range depends on the transfer output type setting. Refer to
Section 6 Parameters
in the
E5
@
D
Digital Temperature Controller User’s Manual
(Cat. No. H224).
Summary of Contents for E5 D Series
Page 2: ......
Page 20: ...18 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 28: ...1 Communications Methods 1 8 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 205: ...I 1 E5 D Digital Temperature Controllers Communications Manual H225 I Index ...
Page 208: ...I 4 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 209: ......