6 Programless Communications
6 - 38
E5@D Digital Temperature Controllers Communications Manual (H225)
6-6
Connecting to the NX1P2
The following configuration is used as an example in giving the setup and application procedures for
programless communications.
•
The same model is used for all of the E5CD Controllers. (The parameter settings cannot be copied if
the models are different.)
•
D0000 to D0089 are used in the PLC memory. The default E5CD parameter allocations are used.
•
You can use either a cross cable or straight cable for the Ethernet cable connection.
Note: Refer to the
Sysmac Studio Version 1 Operation Manual
(Cat. No. W504) for information on installing the
Sysmac Studio.
The application procedure is given below.
6-6-1
Configuration and Procedure
1
2
3
4
5
6
O
N
Computer
IBM PC/AT or compatible
Support Software
Sysmac Studio
Ethernet cable
Back of NX1W-CIF11
DIP switch for operation
settings
RS-485
E5CD
No.0
E5CD
No.1
E5CD
No.2
RS-422A/RS-485 Option Board
NX1W-CIF11
NX-series NX1P2 CPU Unit
NX1P2-9024DT
Built-in EtherNet/IP
port
START
Switch Settings and Wiring
PLC Setup
E5
D Controller Setup
Checking Operation
END
Set the switches on the NX1W-CIF11 and wire it to
the E5CD Controllers.
Use the Sysmac Studio to set up communications on
the NX1W-CIF11 to enable communicating with the
E5CD Controllers.
Set up programless communications in the E5CD
Controllers.
Use the Sysmac Studio to confirm that programless
communications are operating.
Summary of Contents for E5 D Series
Page 2: ......
Page 20: ...18 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 28: ...1 Communications Methods 1 8 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 205: ...I 1 E5 D Digital Temperature Controllers Communications Manual H225 I Index ...
Page 208: ...I 4 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 209: ......