3 - 5
3 Communications Data for CompoWay/F
E5@D Digital Temperature Controllers Communications Manual (H225)
3-1 Variab
le Area (
S
et
tin
g
Ra
n
ge)
List
3
Variable
type
Address
Parameter name
Setting (monitor) value
Level
C1 (81)
0024
Manual MV
Standard control:
H'FFFFFFCE to H'0000041A (
−
5.0 to 105.0)
Heating and cooling control:
H'FFFFFBE6 to H'0000041A (
−
105.0 to 105.0)
Manual
Control
C1 (81)
0025
SP Ramp Set
Value
H'00000000 (0): OFF
H'00000001 to H'0000270F (1 to 9999)
Adjustment
C1 (81)
0026
MV Upper Limit
Standard control:
MV lower limit + 0.1 to H'0000041A
(MV lower limit + 0.1 to 105.0)
Heating and cooling control:
H'00000000 to H'0000041A (0.0 to 105.0)
C1 (81)
0027
MV Lower Limit
Standard control:
H'FFFFFFCE to MV upper limit
−
0.1
(
−
5.0 to MV upper limit
−
0.1)
Heating and cooling control:
H'FFFFFBE6 to H'00000000 (
−
105.0 to 0.0)
C1 (81)
0028
Move to Protect
Level
H'FFFFF831 to H'0000270F (-
−
1999 to 9999)
Protect
C1 (81)
0029
Password to Move
to Protect Level
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
(Can only be set. The monitor value is always
H'00000000.)
C1 (81)
002A
Parameter Mask
Enable
H'00000000 (0): OFF
H'00000001 (1): ON
C1 (81)
002B
PF Key Protect
H'00000000 (0): OFF
H'00000001 (1): ON
C1 (81)
002C
MV Change Rate
Limit
H'00000000 to H'000003E8 (0.0 to 100.0)
Adjustment
C1 (81)
0031
Extraction of
Square Root
Low-cut Point
H'00000000 to H'000003E8 (0.0 to 100.0)
C1 (81)
0032
Alarm Value 4
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
C1 (81)
0033
Alarm Value Upper
Limit 4
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
C1 (81)
0034
Alarm Value Lower
Limit 4
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
C1 (81)
0035
SP 4
SP lower limit to SP upper limit
C1 (81)
0036
SP 5
SP lower limit to SP upper limit
C1 (81)
0037
SP 6
SP lower limit to SP upper limit
C1 (81)
0038
SP 7
SP lower limit to SP upper limit
C1 (81)
0039
Proportional Band
(Cooling)
H'00000001 to H'0000270F (0.1 to 999.9)
C1 (81)
003A
Integral Time
(Cooling)
H'00000000 to H'0000270F
(0 to 9999: Integral/derivative time unit is 1 s.)
(0.0 to 999.9: Integral/derivative time unit is 0.1 s.)
C1 (81)
003B
Derivative Time
(Cooling)
H'00000000 to H'0000270F
(0 to 9999: Integral/derivative time unit is 1 s.)
(0.0 to 999.9: Integral/derivative time unit is 0.1 s.)
C1 (81)
003C
SP Ramp Fall
Value
H'FFFFFFFF (
−
1): Same (Same as SP Ramp Set
Value.)
H'00000000(0): OFF
H'00000001 to H'0000270F (1 to 9999)
Adjustment
C1 (81)
003D
Work Bit 1 ON
Delay
H'00000000 to H'0000270F (0 to 9999)
C1 (81)
003E
Work Bit 1 OFF
Delay
H'00000000 to H'0000270F (0 to 9999)
Summary of Contents for E5 D Series
Page 2: ......
Page 20: ...18 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 28: ...1 Communications Methods 1 8 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 205: ...I 1 E5 D Digital Temperature Controllers Communications Manual H225 I Index ...
Page 208: ...I 4 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 209: ......