6 - 47
6 Programless Communications
E5@D Digital Temperature Controllers Communications Manual (H225)
6-6
Con
nect
ing
to t
h
e N
X
1P2
6
6-
6-5 Che
ckin
g Ope
ration
Changing E5CD Settings
(1) Initialize the download areas with the set values from the E5CD Controllers.
The download areas have not been initialized, so we will initialize them with the set values
from the E5CD Controllers.
Enter 2 (download area initialization) as the value of D015 (Request Flag) in the Watch Tab
Page and press the
Enter
Key. D015 to D029 is the download area for the No. 0 Controller
(E5CD), D045 to D059 is the download area for the No. 1 Controller, and D075 to D089 is
the download area for the No. 2 Controller.
The following parameters are displayed in the download area for the default settings.
(2) Confirm that the download areas have been initialized.
When initialization is completed, D000 (Response Flag) will change to 1 (Normal End) and
D015 (Request Flag) will automatically change to 1 (Enable Writing). Check the download
areas to see if they have been initialized to the values given in the above table.
No.0
No.1
No.2
Parameter
Value
D015
D045
D075
Request Flag (fixed)
1 (0001 hex)
D016
D046
D076
Operation Command Code
(fixed)
0 (0000 hex)
D017
D047
D077
Set Point
0 (0000 hex)
D018
D048
D078
Proportional Band
80 (0050 hex)
D019
D049
D079
Integral Time
233 (00E9 hex)
D020
D050
D080
Derivative Time
40 (0028 hex)
D021
D051
D081
Alarm Value 1
0 (0000 hex)
D022
D052
D082
Alarm Value Upper Limit 1
0 (0000 hex)
D023
D053
D083
Alarm Value Lower Limit 1
0 (0000 hex)
D024
D054
D084
Alarm Value 2
0 (0000 hex)
D025
D055
D085
Alarm Value Upper Limit 2
0 (0000 hex)
D026
D056
D086
Alarm Value Lower Limit 2
0 (0000H hex)
D027
D057
D087
Heater Burnout Detection 1
0 (0000 hex)
D028
D058
D088
PV Input Shift
0 (0000 hex)
D029
D059
D089
SP Ramp Set Value
0 (0000 hex)
No.1 (D015 to D029)
No.2 (D045 to D059)
No.3 (D075 to D089)
Summary of Contents for E5 D Series
Page 2: ......
Page 20: ...18 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 28: ...1 Communications Methods 1 8 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 205: ...I 1 E5 D Digital Temperature Controllers Communications Manual H225 I Index ...
Page 208: ...I 4 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 209: ......