DA 56, DAF 56
6-0-5 XX
Differential pressure controller
2007.07
Technical description
Application:
Heating and cooling systems with variable flow.
Function:
Differential pressure control over the load.
DA 56: Installation in return pipe.
DAF 56: Installation in inlet pipe.
Pressure class:
PN 25 or PN 6 (DN 00 and 25)
Max. differential pressure:
600 kPa = 6 bar
Temperature:
Max. working temperature: 40°C
Min. working temperature: -0°C
Setting range:
Differential pressure adjustable in ranges 5-30, 0-60,
0-00 and 60-50 kPa.
Media:
Water and neutral fluids, water-glycol mixtures.
Material:
Valve body: Ductile iron EN-GJS-400-8LT
Diaphragms and gaskets: EPDM
Adjustment ring: DN 5-50 Ryton plastic,
DN 65-25 R St 37-2 steel.
Surface treatment:
Electrophoretic painting.
Marking:
TA, DN, PN, GGG 40.3, Kvs,
D
p and flow direction arrow.
Flanges:
DN 5-50 (optional): According to EN-092-2:997, type 6.
DN 65-25: According to EN-092-2:997, type 2.