3 Communications Data for CompoWay/F
3 - 12
E5@D Digital Temperature Controllers Communications Manual (H225)
*1
The setting (monitor) range depends on the transfer output type setting. (Refer to
Section 5 Parameters
in
the
E5
@
D Digital Temperature Controllers User's Manual
(Cat. No. H224).)
*2
After communications parameters have been changed, reset the Digital Controller to enable them.
Variable
type
Address
Parameter name
Setting (monitor) value
Level
C3 (83)
0038
Alarm 1 ON Delay
H'00000000 to H'000003E7 (0 to 999)
Advanced
function
setting
C3 (83)
0039
Alarm 2 ON Delay
H'00000000 to H'000003E7 (0 to 999)
C3 (83)
003A
Alarm 3 ON Delay
H'00000000 to H'000003E7 (0 to 999)
C3 (83)
003B
Alarm 1 OFF Delay H'00000000 to H'000003E7 (0 to 999)
C3 (83)
003C
Alarm 2 OFF Delay H'00000000 to H'000003E7 (0 to 999)
C3 (83)
003D
Alarm 3 OFF Delay H'00000000 to H'000003E7 (0 to 999)
C3 (83)
003E
Transfer Output
Type
H'00000000 (0): OFF
H'00000001 (1): Set point
H'00000002 (2): Set point during SP ramp
H'00000003 (3): PV
H'00000004 (4): MV (heating)
H'00000005 (5): MV (cooling)
Initial
setting
C3 (83)
003F
Transfer Output
Upper Limit
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
*1
C3 (83)
0040
Transfer Output
Lower Limit
H'FFFFF831 to H'0000270F (
−
1999 to 9999)
*1
C3 (83)
0041
Control Output 1
Signal
H'00000000 (0): 4 to 20 mA
H'00000001 (1): 0 to 20 mA
C3 (83)
0045
RT
H'00000000 (0): OFF
H'00000001 (1): ON
Advanced
function
setting
C3 (83)
0046
HS Alarm Use
H'00000000 (0): OFF
H'00000001 (1): ON
C3 (83)
0047
HS Alarm Latch
H'00000000 (0): OFF
H'00000001 (1): ON
C3 (83)
0048
HS Alarm
Hysteresis
H'00000001 to H'000001F4 (0.1 to 50.0)
C3 (83)
0049
LBA Detection
Time
H'00000000 to H'0000270F (0 to 9999)
C3 (83)
004A
LBA Level
H'00000001 to H'0000270F
(0.1 to 999.9 for temperature input)
(0.01 to 99.99 for analog input)
C3 (83)
004B
LBA Band
H'00000000 to H'0000270F
(0.0 to 999.9 for temperature input)
(0.00 to 99.99 for analog input)
C3 (83)
004C
Protocol Setting
*2
H'00000000 (0): CompoWay/F
H'00000001 (1): Modbus
H'00000002 (2): Disabled
H'00000003 (3): Host Link (FINS)
H'00000004 (4): MC protocol (Format 4)
H'00000005 (5): Dedicated protocol (Format 4)
Communi
cations
setting
C3 (83)
004D
Send Data Wait
Time
*2
H'00000000 to H'00000063 (0 to 99)
Summary of Contents for E5 D Series
Page 2: ......
Page 20: ...18 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 28: ...1 Communications Methods 1 8 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 205: ...I 1 E5 D Digital Temperature Controllers Communications Manual H225 I Index ...
Page 208: ...I 4 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 209: ......