6 Programless Communications
6 - 12
E5@D Digital Temperature Controllers Communications Manual (H225)
There are 13 upload settings and 13 download settings.
Communications Setting Level
Display condition: The Protocol Setting parameter must be set to
mod
,
fins
,
mcp4
, or
fxp4
.
*
This parameter cannot be used when the Protocol Setting parameter is set to
fxp4
.
z
Example of Changing a Setting:
To set the Alarm Value 3 parameter for Download Setting 11, you would change the set value from 45
(Heater Burnout Detection 1) to 38 (Alarm Value 3).
Parameter name
Displayed
characters
Setting range
Default
Communications
Node Number
unit
0 to 99
0
6-2-9
Upload Settings and Download Settings
Parameter name
Displayed characters
Setting range
Default
Upload Setting 1
up01
0 to 108
1
Communications Monitor
Upload Setting 2
up02
2
Status (Upper Word)
Upload Setting 3
up03
3
Status (Lower Word)
Upload Setting 4
up04
4
Status 2 (Upper Word)
Upload Setting 5
up05
6
Decimal Point Monitor
Upload Setting 6
up06
7
Process Value
Upload Setting 7
up07
8
Internal Set Point
Upload Setting 8
up08
11
Heater Current 1 Value
Monitor
Upload Setting 9
up09
16
MV Monitor (Heating)
Upload Setting 10
up10
0
Nothing assigned.
Upload Setting 11
up11
0
Nothing assigned.
Upload Setting 12
up12
0
Nothing assigned.
Upload Setting 13*
up13
0
Nothing assigned.
Download Setting 1
dn01
30 to 108
31
Set Point
Download Setting 2
dn02
61
Proportional Band
Download Setting 3
dn03
62
Integral Time
Download Setting 4
dn04
63
Derivative Time
Download Setting 5
dn05
32
Alarm Value 1
Download Setting 6
dn06
33
Alarm Value Upper Limit 1
Download Setting 7
dn07
34
Alarm Value Lower Limit 1
Download Setting 8
dn08
35
Alarm Value 2
Download Setting 9
dn09
36
Alarm Value Upper Limit 2
Download Setting 10
dn10
37
Alarm Value Lower Limit 2
Download Setting 11
dn11
45
Heater Burnout Detection 1
Download Setting 12
dn12
57
Process Value Input Shift
Download Setting 13
dn13
75
SP Ramp Set Value
Summary of Contents for E5 D Series
Page 2: ......
Page 20: ...18 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 28: ...1 Communications Methods 1 8 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 205: ...I 1 E5 D Digital Temperature Controllers Communications Manual H225 I Index ...
Page 208: ...I 4 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 209: ......