6 Programless Communications
6 - 46
E5@D Digital Temperature Controllers Communications Manual (H225)
(5) Check the value of parameters set in the upload area.
D000 to D014 is the upload area for the No. 0 Controller (E5CD), D030 to D044 is the
upload area for the No. 1 Controller, and D060 to D074 is the upload area for the No. 2
Controller.
With the default settings, the following parameters are set for the upload areas.
Check the values in the upload area to see if they are the same as those that are given in
the following table.
(It is not necessary to check addresses for which “---” is given in the
Value
column.)
*
If the default settings are used and a sensor is not connected, the PV display on the E5CD will show an input
error and the process value in the upload area will be 1320 (528 hex).
No.0
No.1
No.2
Parameter
Value
D000
D030
D060
Response Flag (fixed)
0
D001
D031
D061
Communications Status (fixed)
Alternates between 0 and 1.
D002
D032
D062
Communications Monitor
---
D003
D033
D063
Status (Upper Word)
---
D004
D034
D064
Status (Lower Word)
---
D005
D035
D065
Status 2 (Upper Word)
---
D006
D036
D066
Decimal Point Monitor
---
D007
D037
D067
PV
PV*
D008
D038
D068
Internal Set Point
---
D009
D039
D069
Heater Current 1 Value Monitor
---
D010
D040
D070
MV Monitor (Heating)
---
D011
D041
D071
Spare
---
…
…
…
…
…
D014
D044
D074
Spare
---
No.1 (D000 to D014)
No.2 (D030 to D044)
No.3 (D060 to D074)
Summary of Contents for E5 D Series
Page 2: ......
Page 20: ...18 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 28: ...1 Communications Methods 1 8 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 205: ...I 1 E5 D Digital Temperature Controllers Communications Manual H225 I Index ...
Page 208: ...I 4 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 209: ......