3 Communications Data for CompoWay/F
3 - 24
E5@D Digital Temperature Controllers Communications Manual (H225)
z
Status 2 Details
Note1 “Spare” bits are always OFF.
2 When read in setup area 1, the status of the bits will be as follows:
Bit position
Status
Bit Description
0
1
Status
(lower
word)
0
Work bit 1
OFF
ON
1
Work bit 2
OFF
ON
2
Work bit 3
OFF
ON
3
Work bit 4
OFF
ON
4
Work bit 5
OFF
ON
5
Work bit 6
OFF
ON
6
Work bit 7
OFF
ON
7
Work bit 8
OFF
ON
8
Spare
OFF
---
9
Spare
OFF
---
10
Spare
OFF
---
11
Spare
OFF
---
12
Spare
OFF
---
13
Spare
OFF
---
14
Spare
OFF
---
15
Spare
OFF
---
Status
(upper
word)
16
Event input 5
OFF
ON
17
Event input 6
OFF
ON
18
Spare
OFF
---
19
Spare
OFF
---
20
Invert direct/reverse operation
Not invert
Invert
21
SP ramp
OFF
During SP ramp
22
Adaptive control in progress (system
performance evaluation)
OFF
ON
23
Adaptive control notification in
progress
OFF
ON
24
Automatic filter adjustment in
progress
OFF
ON
25
Adaptive control PID update enabled No updateable PID
Updateable PID
26
Spare
OFF
---
27
Spare
OFF
---
28
Alarm 4
OFF
ON
29
Spare
OFF
---
30
Spare
OFF
---
31
Spare
OFF
---
•
Work bits 1 to 8:
Cleared
•
SP ramp:
Last value held
•
Adaptive control in progress (system performance evaluation): Cleared
•
Adaptive control notification in progress:
Cleared
•
Automatic filter adjustment in progress:
Cleared
•
Alarm outputs:
Cleared
•
Adaptive control PID update enabled:
Cleared
Summary of Contents for E5 D Series
Page 2: ......
Page 20: ...18 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 28: ...1 Communications Methods 1 8 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 205: ...I 1 E5 D Digital Temperature Controllers Communications Manual H225 I Index ...
Page 208: ...I 4 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 209: ......