2 CompoWay/F Communications Procedures
2 - 16
E5@D Digital Temperature Controllers Communications Manual (H225)
(2) Response Code
•
Normal Completion
•
Error Occurred
•
Service Request PDU
•
Service Response PDU
(1) Command Code and Related Information
Response code
Name
Description
0000
Normal completion
No errors were found.
Response code
Error name
Description
1001
Command too long
The command is too long.
2203
Operation error
Non-volatile memory error
2-3-8
Operation Command
•
Communications Writing
•
RUN/STOP
•
Multi-SP
•
AT Execute/Cancel
•
Write Mode
•
Save RAM Data
•
Software Reset
•
Move to Setup Area 1
•
Move to Protect Level
•
Auto/Manual Switch
•
Parameter Initialization
•
Alarm Latch Cancel
•
Invert Direct/Reverse
Operation
•
PID Update (Adaptive Control)
•
Program Start
•
Automatic Filter Adjustment
Command code
Command content
Related Information
00
Communications Writing
00: OFF (disabled)
01: ON (enabled)
01
RUN/STOP
00: Run
01: Stop
02
Multi-SP
00: Set point 0
01: Set point 1
02: Set point 2
03: Set point 3
04: Set point 4
05: Set point 5
06: Set point 6
07: Set point 7
03
AT Execute/Cancel
00: AT cancel
01: 100% AT execute
02: 40% AT execute
MRC SRC
3 0 0 5
2
2
2
2
Com-
mand
code
Related
informa-
tion
MRC SRC
3 0 0 5
2
2
4
Response
code
Summary of Contents for E5 D Series
Page 2: ......
Page 20: ...18 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 28: ...1 Communications Methods 1 8 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 205: ...I 1 E5 D Digital Temperature Controllers Communications Manual H225 I Index ...
Page 208: ...I 4 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 209: ......