3 Communications Data for CompoWay/F
3 - 14
E5@D Digital Temperature Controllers Communications Manual (H225)
Variable
type
Address
Parameter name
Setting (monitor) value
Level
C3 (83)
0050
Auxiliary Output 1
Assignment
H'00000000 (0): Not assigned.
H'00000001 (1): Control output (heating)
H'00000002 (2): Control output (cooling)
H'00000003 (3): Alarm 1
H'00000004 (4): Alarm 2
H'00000005 (5): Alarm 3
H'00000006 (6): Alarm 4
H'00000007 (7): Heater alarm
H'00000008 (8): HB alarm
H'00000009 (9): HS alarm
H'0000000A (10): Input error
H'0000000B (11): Not assigned.
H'0000000C (12): Program end output
H'0000000D (13): RUN output
H'0000000E (14): Integrated alarm
H'0000000F (15): Work bit 1
*1
H'00000010 (16): Work bit 2
*1
H'00000011 (17): Work bit 3
*1
H'00000012 (18): Work bit 4
*1
H'00000013 (19): Work bit 5
*1
H'00000014 (20): Work bit 6
*1
H'00000015 (21): Work bit 7
*1
H'00000016 (22): Work bit 8
*1
Advanced
function setting
C3 (83)
0051
Auxiliary Output 2
Assignment
H'00000000 to H'00000016 (0 to 22)
Note: Same as for the Auxiliary Output 1
Assignment parameter.
C3 (83)
0053
Program Pattern
H'00000000 (0): OFF
H'00000001 (1): STOP
H'00000002 (2): CONT
Initial setting
C3 (83)
0054
Soak Time Unit
H'00000000 (0): Minutes
H'00000001 (1): Hours
H'00000002 (2): Seconds
Advanced
function setting
C3 (83)
0055
Alarm SP Selection
H'00000000 (0): Set point during SP ramp
H'00000001 (1): Set point
C3 (83)
0056
Auxiliary Output 3
Assignment
H'00000000 to H'00000016 (0 to 22)
Note: Same as for the Auxiliary Output 1
Assignment parameter.
C3 (83)
005B
Manual MV Limit
Enable
H'00000000 (0): OFF
H'00000001 (1): ON
C3 (83)
005D
AT Calculated Gain
H'00000001 to H'00000064 (0.1 to 10.0)
C3 (83)
005E
AT Hysteresis
H'00000001 to H'0000270F
(0.1 to 999.9 for temperature input)
(0.01 to 9.99 for analog input)
C3 (83)
005F
Limit Cycle MV
Amplitude
H'00000032 to H'000001F4 (5.0 to 50.0)
C3 (83)
0067
PV Rate of Change
Calculation Period
H'00000001 to H'000003E7 (1 to 999)
C3 (83)
0068
Heating/Cooling
Tuning Method
H'00000000 (0): Same (Same as for heating.)
H'00000001 (1): Linear
H'00000002 (2): Air cooling
H'00000003 (3): Water cooling
C3 (83)
006C
Extraction of Square
Root Enable
H'00000000 (0): OFF
H'00000001 (1): ON
*1
You cannot set these values if you do not use the logic operation function.
Summary of Contents for E5 D Series
Page 2: ......
Page 20: ...18 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 28: ...1 Communications Methods 1 8 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 205: ...I 1 E5 D Digital Temperature Controllers Communications Manual H225 I Index ...
Page 208: ...I 4 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 209: ......