(2) Response Code
•
Normal Completion
•
Error Occurred
04
Write Mode
00: Backup
01: RAM write mode
05
Save RAM Data
00
06
Software Reset
00
07
Move to Setup Area 1
00
08
Move to Protect Level
00
09
Auto/Manual Switch
00: Automatic mode
01: Manual mode
0B
Parameter Initialization
00
0C
Alarm Latch Cancel
00: Alarm 1 latch cancel
01: Alarm 2 latch cancel
02: Alarm 3 latch cancel
03: HB alarm latch cancel
04: HS alarm latch cancel
05: Alarm 4 latch cancel
0F: All alarm latch cancel
0D
SP Mode
00: Local SP mode
01: Remote SP mode
0E
Invert Direct/Reverse Operation
00: Not invert
01: Invert
0F
PID Update (Adaptive Control)
00
11
Program Start
00: Reset
01: Start
12
Automatic Filter Adjustment
00: OFF
01: ON
Response code
Name
Description
0000
Normal completion
No errors were found.
Response code
Error name
Description
1001
Command too long
The command is too long.
1002
Command too short
The command is too short.
1100
Parameter error
Command code and related
information are wrong.
2203
Operation error
•
The Communications Writing
parameter is set to "OFF"
(disabled). The command is
received regardless of the
Communications Writing
parameter setting (ON/OFF).
•
Processing could not be
performed. For details, refer to
(3) Operation Commands and
Precautions
below.
•
Non-volatile memory error
Command code
Command content
Related Information
Summary of Contents for E5 D Series
Page 2: ......
Page 20: ...18 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 28: ...1 Communications Methods 1 8 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 205: ...I 1 E5 D Digital Temperature Controllers Communications Manual H225 I Index ...
Page 208: ...I 4 E5 D Digital Temperature Controllers Communications Manual H225 ...
Page 209: ......