4 TROUBLESHOOTING
4.7 Event List
237
4
Security
Operation
00C65
Time synchronization receive processing failure
The receive processing for time synchronization failed.
00C70
CANopen initialization failure
A communication error occurs in CANopen initialization processing.
00C71
Initialization failure (parameter mismatch between
master and slave stations)
During initialization processing at the start of control communication, a parameter
mismatch was detected between the master station and slave stations.
00C72
Maximum response time mismatch during time-
managed polling
A mismatch was detected in the maximum response time during time-managed polling.
Update the version of the engineering tool and the slave stations to the latest version,
and then retry the operation.
00C80
Slave station that does not support CC-Link IE TSN
Protocol version 2.0 detected
A slave station that does not support CC-Link IE TSN Protocol version 2.0 was detected.
00C81
CC-Link IE TSN Class settings mismatch
A mismatch was detected between the parameter of the master station and the CC-Link
IE TSN Class of the slave stations.
Event
code
Overview
Cause
10200
Remote password lock
The lock processing of the remote password was performed.
10201
Remote password unlock successful
The unlock processing of the remote password was succeeded.
10202
Remote password unlock failed
The unlock processing of the remote password has failed.
10300
Access from IP restricted with IP filter setting
Accessed from IP address restricted with the IP filter setting.
Event
code
Overview
Cause
24100
Own station: Parameter change/new parameter
reception
Parameter was changed. Or new parameter was received at power-on.
24300
Own station: Enabling remote device test function
Remote device test function was enabled.
24301
Own station: Failure in enabling remote device test
function (Programmable controller CPU is not in STOP
state (excluding a stop error))
The operating status of the programmable controller CPU is not in STOP state
(excluding a stop error), and enabling remote device test function failed.
24302
Own station: Failure in enabling remote device test
function (Own station is not set as a master station.)
The own station is not set as a master station and enabling remote device test function
failed.
24303
Own station: Disabling remote device test function
(SB0016 is turned off.)
Remote device test function was disabled because SB0016 (Remote device forced
output request) has been turned off.
24304
Own station: Disabling remote device test function
(Programmable controller CPU is in RUN or PAUSE
state).
Remote device test function was disabled because operating status of the
programmable controller CPU has been changed to RUN or PAUSE state.
24305
Own station: Disabling remote device test function
(Programmable controller CPU indicates a stop error.)
Remote device test function was disabled because a stop error has occurred in the
programmable controller CPU.
24307
Network number, station number, IP address setting/
change execution
Setting or change of the network number, station number, or IP address of the own
station was executed.
24F00
Another station: CPU operating status change
detection
Operating status of the CPU module on another station was changed.