2 PARAMETER SETTINGS
2.5 "CC-Link IE TSN Configuration" Window
121
2
Connected/Disconnected Module Detection
Connected slave stations are detected and displayed on the "CC-Link IE TSN Configuration" window.
When setting up a network system, it is easier to create parameters when changing the network system configuration.
If this function is performed immediately after a slave station is connected, the information of the connected device may not be
correctly read out. In this case, retry the operation.
1.
Click the [Connected/Disconnected Module Detection] button.
2.
When the [Execute] button is clicked according to the instruction on the window, connected slave stations are detected
and displayed on the "CC-Link IE TSN Configuration" window.
3.
Check items in the list of stations and change them as necessary. (
4.
Select [Close with Reflecting the Setting] and close the "CC-Link IE TSN Configuration" window.
Detection of connected/disconnected devices cannot be executed in the following cases.
• The RJ71GN11-T2 is not in online mode. (
Page 111 Module Operation Mode)
• "Link Direct Device Setting" of the CPU parameter is not "Extended Mode (iQ-R Series Mode)".
• When multiple numbers of the RJ71GN11-T2 are mounted on the base unit, and the module that has the
smallest slot number is a local station, the local station is not in the online mode, or that station is in data link
error.
• The actual system configuration is incorrect. (An overlapping IP address or others)
• The version of the engineering tool is "1.082L" or earlier and the data link of the master station is incorrect.
• The firmware version of the RJ71GN11-T2 is "14" or earlier and the data link of the master station is
incorrect.