4 TROUBLESHOOTING
4.5 List of Error Codes
223
4
D25FH
A remote instruction was executed from the
module with a station type which cannot
execute it.
Stations other than the master station cannot execute a remote instruction.
Modify the program so that remote instructions are not executed from
stations that cannot use them.
D260H
A remote instruction was executed from the
module with a station type which cannot
execute it.
Stations other than the master station cannot execute a remote instruction.
Modify the program so that remote instructions are not executed from
stations that cannot use them.
D262H
The total number of slave stations specified
in the CCPASET instruction is incorrect.
• Execute the instruction again after correcting the total number of slave
stations in the control data.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
D263H
The constant link scan time setting of the
CCPASET instruction is incorrect.
• Execute the instruction again after correcting the constant link scan time
in the control data.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
D264H
The station number setting of the CCPASET
instruction is incorrect.
• Execute the instruction again after correcting the station number in the
network configuration setting data so it is within 1 to 120.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
D265H
The station number specified for the
CCPASET instruction is already in use.
• Execute the instruction again after correcting the station number in the
network configuration setting data to a unique value.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
D266H
The number of occupied stations specified in
the CCPASET instruction is incorrect.
• Execute the instruction again after correcting the number of occupied
stations in the network configuration setting data.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
D267H
The station type of the CCPASET instruction
is incorrect.
• Execute the instruction again after correcting the station type in the
network configuration setting data.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
D268H
The link device range assignment specified
for each station in the CCPASET instruction
is incorrect.
• Execute the instruction again after correcting the offset or the number of
points of link devices in the network configuration setting data.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
D269H
The station type of the REMFR/REMTO/
REMFRD/REMTOD/REMFRIP/REMFRDIP/
REMTOIP/REMTODIP instruction target
station is not a remote station.
• Set the station type of the REMFR/REMTO/REMFRD/REMTOD/
REMFRIP/REMFRDIP/REMTOIP/REMTODIP instruction target station to
a remote station.
• Correct the network number and station number/IP address of the target
station of the dedicated instruction.
D26AH
The target station of the REMFR/REMTO/
REMFRD/REMTOD/REMFRIP/REMFRDIP/
REMTOIP/REMTODIP instruction does not
exist.
If the target station of the REMFR/REMTO/REMFRD/REMTOD/REMFRIP/
REMFRDIP/REMTOIP/REMTODIP instruction is disconnected, execute the
dedicated instruction again after return of the target station.
D26BH
The network number setting of the
CCPASET instruction executing station is
incorrect.
Set "Network No." under "Network No." of "Required Settings" to between 1
and 239.
D26CH
The station type and station number of the
CCPASET instruction executing station are
incorrect.
Rewrite the module parameter using the engineering tool. If the same error
occurs again even after taking the above, the possible cause is a hardware
failure of the error module. Please consult your local Mitsubishi
representative.
D273H
The request data size of transient
transmission is incorrect.
• Correct the request command at the transient request source, and retry
the operation.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
D275H
Other dedicated instructions are in
execution, and the executed instruction
cannot be processed.
• Execute the instruction again after a while.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
D27AH
The own station number set in the UINI
instruction is incorrect.
• Set the station number of the own station in the control data to a value
from 1 to 120, and retry the operation.
• If the error occurs again even after taking the above, please consult your
local Mitsubishi representative.
Error
code
Error definition and causes
Action
Detailed
information 1
Detailed
information 2
Summary of Contents for MELSEC iQ-R CC-Link IE TSN
Page 1: ...MELSEC iQ R CC Link IE TSN User s Manual Application RJ71GN11 T2 ...
Page 2: ......
Page 323: ...APPX Appendix 10 Added and Enhanced Functions 321 A MEMO ...
Page 325: ...I 323 MEMO ...
Page 329: ......