4 TROUBLESHOOTING
4.1 Checking with LED
■
If the RJ71GN11-T2 with a firmware version of "11" or earlier is used
If the RJ71GN11-T2 with a firmware version of "11" or earlier is used, also check the following items.
Check item
Action
Is a data link faulty station displayed on the "CC-
Link IE TSN/CC-Link IE Field Diagnostics"
window?
■
When the communication speed of the data link faulty station is 100Mbps, and the communication speed
of the master station is 1Gbps
Take either of the following actions for wiring and setting.
• Use either P1 or P2 of the master station.
• Connect the data link faulty station to a multicast filter supported device and activate the multicast
mode. (
Manual of the device used)