3 PROGRAMMING
3.1 Precautions for Programming
3
PROGRAMMING
This chapter describes programming and startup examples of CC-Link IE TSN.
3.1
Precautions for Programming
This section describes precautions to create CC-Link IE TSN programs.
Cyclic transmission program
For a cyclic transmission program, configure an interlock with the following module labels (link special relay (SB), link special
register (SW)).
• 'Data link error status of own station' (SB0049)
• 'Data link status of each station' (SW00B0 to SW00B7)
Program using safety communications
For a program using safety communications, interlock with the safety special register described below. (For the 1st master/
local module)
• 'Safety refresh communication status of each safety connection (1st module)' (SA\SD1008 to SA\SD1015)
For a communication example using the safety communications, refer to the following.
• Communication Example of Safety Communications (
Page 145 Communication Example of Safety Communication)